7.2 CLEANING THE HEAT EXCHANGER
Every year, verify that the fin pack is not clogged from dust or anything else that does
not allow the normal airflow; if necessary, use a jet of compressed air to clean the heat
exchanger. To prevent damage to the fins, or the pipes on the heat exchanger, never use
steel tools or sharp objects to clean the spaces between the fins. The access to the fin pack
is possible only after having disconnected the unit from the power mains and after removing
the filter.
7.3 TROUBLESHOOTING
Here is a list of possible problems and malfunctions, their causes and the procedures that
you or the technical service must perform to correct the malfunction.
PROBLEM
The unit does not deliver air
POSSIBLE CAUSE
Lack on the power supply
Set point reached
In presence of WS, hot water
temperature <35°C, insufficient
water flow and/or temperature
in coil, or damaged WS (water
sensor)
Electric motor burnt
LEGEND
1.
Filter
2.
Filter cover panel
3.
Screw 3,9x32
4.
Screw 3,9x9,5
SOLUTION
Verify the network voltage and/
or integrity of the fuse on the
control's electronic card and
the rightness of the electrical
connections
Check the control setting
Check the water temperature and
water flow on the coil and/or the
correct working of the WS (water
sensor)
Replace the faulty component