Télécharger Imprimer la page

EURAPO EBH 020 Manuel D'utilisation Et Installation page 34

Unité gainable

Publicité

Les langues disponibles

Les langues disponibles

1
2
3
EBH unit with right water connections
4
NOTE: The internal diameter of the connection piping to these units has to be
bigger than 28 mm. The above mentioned connection piping must be properly
5
insulated.
Piping path has to be defined in order not to interfere with the removal of the metal cover
panels on the bottom side of the unit.
6
To facilitate installation and maintenance, we recommend that manual shut-off valves are
installed on the intake and outlet pipes, and that a mechanical «Y» filter is interposed
between the valve and the inlet of the heat exchanger, in order to prevent the clogging of
7
the heat exchanger.
8
6.4.1 HYDRAULIC CONNECTIONS
9
10
+
MAX. TIGHTENING TORQUE FOR THE CONNECTION OF THE EURAPO VALVE
KIT IS 25 Nm
Use protection glasses to avoid hot water spays on the eyes during air bleeding
operation
The coils for sizes 020÷050, are provided with air-vents/water drainage valves, accessible by us-
ing a screwdriver through the holes on the side of the inner frame.
On sizes 060-070 the air-vent valves are not included, therefore it is necessary to prearrange on
the water piping a device for the water discharge and air vent from the coil.
34
During hydraulic connection phases, it is recom-
mended to pay attention not to exert excessive
force when tightening the connections and in
case to use a double pipe wrench to avoid an over
tightening and irreparable damages to the coil.
2 PIPE SYSTEM
1. Water inlet ..............................................1" M
2. Water outlet ..........................................1" M
4 PIPE SYSTEM
1. Inlet cooling water ..........................1" M
2. Outlet cooling water .....................1" M
3. Inlet heating water ..........................1" M
4. Outlet heating water .....................1" M
5. Condensate drain hose ....... ø20 mm
6. Electric box