Hysteresis Mode
The change of state occurs when a threshold is detected
(increasing temperature: high threshold (OHI) to be detected,
decreasing temperature: low threshold (OLO) to be detected).
Not inverted
Contact
ON
OFF
OLO
OHI
Window Mode
The change of state occurs when any
threshold is detected.
Not inverted
Contact
ON
OFF
OLO
OHI
The delay (DEL) is set for the both switching
thresholds. The switching only occurs when
either threshold value (OHI - OLO) is exceeded
for a duration higher than the DEL delay.