• Table 1a
Maximum load of refrigerant permitted in one room: internal unit 8/10 kW
Length of the pipes
(m)
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
•
Table 1b
Maximum load of refrigerant permitted in one room: internal unit 12/14/16 kW
Length of the pipes
(m)
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
EN - 10
Load of refrigerant
(kg)
1.650
1.688
1.726
1.764
1.802
1.840
1.878
1.916
1.954
1.992
2.030
2.068
2.106
2.144
2.182
2.220
Load of refrigerant
(kg)
1,840
1,878
1,916
1,954
1,992
2,030
2,068
2,106
2,144
2,182
2,220
2,258
2,296
2,334
2,372
2,410
A
(m
)
A
2
roomMIN
H=1100mm
-
-
-
-
-
-
8,93
9,30
9,67
10,05
10,43
10,83
11,23
11,64
12,06
12,48
A
(m
)
A
2
roomMIN
H=1100mm
-
4,53
4,62
4,71
4,81
4,90
4,99
5,08
5,17
5,26
5,36
5,45
5,54
5,63
5,72
5,81
(m
)
2
roomMIN
H=1800mm
-
-
-
-
-
-
4,53
4,62
4,71
4,81
4,90
4,99
5,08
5,17
5,26
5,36
(m
)
2
roomMIN
H=1800mm
-
8,93
9,30
9,67
10,05
10,43
10,83
11,23
11,64
12,06
12,48
12,91
13,35
13,79
14,25
14,71