Press the icon with the diagram to access the
trend of the temperatures acquired in the last
hour of operation screen.
To move inside the diagram:
- Press the right or left arrow to move the cursor.
- Press directly on the diagram to move to the desired position.
5.9 - SOFTWARE UPDATE
In case it is necessary to update the software of the internal unit, proceed as follows:
a. From the System screen, check the software versions of the display board and power board
• Proceed with the software update only if strictly necessary
• Each software update entails the rewriting of Service parameters to their factory value. At the
end of the updated, all or part of these parameters will have to be manually and opportunely
reconfigure to adapt them to your own system.
b. Empty an USB memory device completely (it must be without files and folders)
c. Load the files listed below in the USB memory device
OLMP_PDC_PU2.bin
Update.Fw
Update.fw.md5
updateFw
d. Disconnect all power supplies, of both the internal and external unit
e. Connect the USB memory device in port USB1 of the power board
f.
Power the internal unit
g. The power board software update starts automatically. At its completion, the display of the internal unit
is operational again.
h. Disconnect all power supplies. Remove the USB memory device.
i.
Connect the USB flash drive to port USB2 of the display board
l.
Power the internal unit
m. The display board software update starts automatically. At its completion, the display of the internal unit
is operational again.
n. Disconnect all power supplies. Remove the USB memory device.
o. Restore all power supplies.
p. Access page MENU -> SERVICE and press "RESET" to update all parameters.
q. From System screen, check that the display and power boards software versions are correct.
r.
Access parameters "ADDR370" and "ADDR371" to configure the heat pump correctly.
6 - MANAGEMENT AND CONTROLS
6.1 - INTERNAL UNIT ADDITIONAL ELECTRIC HEATERS MANAGEMENT
The internal unit is equipped with two electric heaters. The electric heaters are enabled to integrate power
in heating mode, domestic water production mode, during the execution of the Anti-Legionella cycles or for
start-up of the system in case of low temperatures or in building sites for screed drying.
Parameter "ADDR217"
0 = not enabled
1 = one heater enabled for backup
2 = two heaters enabled for backup
3 = one heater enabled for low-temperature start
4 = two heaters enabled for low-temperature start
6.1.1 - Backup
The first electric heater EH1 activates if:
- The heat pump has been in heating mode or domestic hot water production mode for at least ADDR235
minutes.
- The external ambient temperature is lower than ADDR227 degrees Centigrade.
- The delta on water is at least 4°K with respect to the setpoint.
After further 15 minutes from the activation of the first electric heater, if these conditions persist, the second
electric heater activates.
The backup function with electric heaters is not active if the external heat source ADDR226 is enabled (ON).
EN - 39