Relay HORN no. 1:
•
is configured as normally de-energized (ND).
•
is not activated if power is OFF or battery is depleted
•
is voted if four out of five conditions are met and
•
is energized if at least four of these conditions are met:
•
Channel 2 goes into alarm 1
•
Channel 3 goes into alarm 2
•
Channel 4 goes into STEL alarm
•
Channel 5 goes into TWA alarm
•
Channel 6 goes into FAULT.
Modifying Output Relays
(1)
Enter into System menu.
(2)
In the System menu, select the item for "Relay Setting Menu" and press [ENTER] to confirm (see
5.1 "System Menu").
The first of two configuration screens displays.
NOTE: Use [DOWN] to toggle between the two screens:
GasGard XL
Configuration
US
29