MSA GasGard XL Manuel D'utilisation page 22

Masquer les pouces Voir aussi pour GasGard XL:

Publicité

Les langues disponibles

Les langues disponibles

5
Configuration
All GasGard XL Control Unit parameters can be configured by using:
front panel control push buttons
configuration software tool (see Chapter 6 "Configuration Software").
Two menus allow the user to change unit parameters:
(1)
System Menu
The System menu:
enables the user to change any parameter needed for application requirements
is accessible only by an access password.
From the System menu, the user can enter additional Control Unit set-up menus:
Relay Setting menu (to set up individual relay parameters)
Calibration menu (to calibrate all channels)
General Setting menu (to set up general unit parameters).
(2)
Calibration Menu
The channel boards are configured to accept 4-20 mA input signals from two-wire or three-wire
remote transmitters. The controller does not require any calibration.
NOTE: There are different passwords for the System menu and Calibration menu. Passwords can be
set in the General Setting menu.
5.1
System Menu
The System menu allows full unit configuration:
Modifying channel parameters
Setting output relays (Relays Setting menu)
Calibration (Calibration menu)
General settings (General setting menu).
(1)
(2)
(3)
Simultaneously Press [ENTER] and [ESCAPE] and hold for one second.
User is prompted to enter the password.
Access Password is any number from 1 to 9999.
The factory password preset value is 123.
Use [UP]; [DOWN] and [ENTER] to enter the password.
Press [ENTER] to confirm the password.
If password is valid, the System menu screen appears.
GasGard XL
Configuration
US
22