Télécharger Imprimer la page

MSA GasGard XL Manuel D'utilisation page 9

Masquer les pouces Voir aussi pour GasGard XL:

Publicité

Les langues disponibles

Les langues disponibles

Display Board
The Display board, located on the back side of the lid, includes:
microcontroller
watchdog
push buttons
graphic display (128x64).
Sensor Extension Board
The sensor extension board is used to:
attach channel boards
connect internal communication.
NOTE: See 3.4 "Sensor Connection".
Channel Board
The channel boards are set to communicate with 4-20 mA transmitters.
Every board:
includes four LEDs (A1, A2, Status, Power)
attaches to the Channel connectors (four on the Main board, four on the Sensor Extension board).
Sensor power and connection is designed as "fail-safe"
(wrong connection/configuration does not damage the remote sensor).
Channel Relay Board
Every Channel Relay board:
provides eight output relays
is connected to the Main board or Sensor Extension board (one by one) via connectors.
Relays are fully user-configurable from the front panel or connected PC via configuration software.
Two optional SPDT (Single Pole Double Throw) relays per channel (eight relays per four channels)
are configurable for individual alarms:
Normally open/closed
Normally energized/de-energized
Latching/non latching
Increasing/decreasing
N out of m voting
Grouping
NOTE: Contacts are resistive load.
Front Panel
The Front Panel enables communication with the Control Unit and is used to:
monitor the status of all connected field sensors
determine system settings
configure all settings.
GasGard XL
Description
US
9

Publicité

loading