Page 1
Installation Instruction and Care Guide Format.zip of Gas-Fired Wall Hung Hot Water Boilers...
Page 2
Fonderie Sime S.p.A. Via Garbo, 27 – 37045 LEGNAGO (VR) declares that: a) The materials used in the interior of the boiler are suitable for the use of drinking water. b) No dangerous toxic substances were used to manufacture the boiler and its components, which could enter the drinking water.
Installation Instruction and User and Care Guide FORMAT.zip of Gas-Fired Wall Hung Hot Water Boilers TABLE OF CONTENTS WARNING DESCRIPTION OF THE BOILER : If the information in this manual is not followed exactly, a fire of explosion may 1. 1...
This booklet provides the instructions for soundness of the connections, inclu- 10. The installer must provide the user the “FORMAT.zip 35 BF” with eletronic igni- ding that of the burner. with instruction in operation of the tion, modulation, and direct sealed forced- 4.
Page 5
CLEARANCES FROM Model 35 BF Units Natural gas Propane COMBUSTIBLE MATERIALS: Bottom: 0 mm (0 in.) Maximum input 39.2 37.3 Sides: 0 mm (0 in.) But/h 133,800 127,300 Rear: 0 mm (0 in.) Front: 0 mm (0 in.) Minimum input 15.7 17.
Page 6
Main exchanger Combustion chamber Gas valve D.H.W. plate exchanger Divertor valve C.H. sensor (SM) 100°C safety stat 10 Pump with automatic air vent 11 Expansion vessel 12 Safety valve 13 Boiler discharge 14 Water flow switch 15 Tridicator 16 Automatic by-pass 17 D.H.W.
INSTALLATION The installation must conform to the require- ting of the burner, combustion chamber or 2.2. 1 Isolating valves kit ments of the Authority having jurisdiction or, in flue passageway. The boilers installed using the absence of such requirement, to the Natio- inside air supply must provide provisions for To fit the isolating valves, supplied with the boi- nal Fuel Gas Code, ANSI Z223.
Page 8
Code”, ANSI Z223. 1 (NFPA 54). Consult the “Natural gas and propane installation code” or “National Flue Gas Code” for the recommen- ded gas pipe size of other materials. The sec- tions of the piping making up the system must be such as to guarantee a supply of gas suffi- cient to cover the maximum demand, limiting pressure loss between the gas meter and any...
The boiler is supplied as standard with a ø 86 3. If a segment of the flue passes through ducts of combustion into the atmosphere diaphragm. With outlet type C12, install diaph- a flammable wall, this segment must be TYPICAL PIPING “FORMAT.ZIP 35 BF”...
Page 10
insulated with a glass wool pipe insula- tor 30 mm (1 in) thick, with a density of 50 kg/m (3lb/f t ) or follow vent manufacturers instructions for clearan- ces to combustibles. 4. The distance between the intake air and the smoke pipe must be within 300 mm (12 in) - (see fig.
Page 11
(ATTENTION! The total length of linear exhaust sections should not exceed 8 m (26 ft) as compared to the total length of 205 (8.07”) linear suction sections). For head losses in the fittings, refer to Table 100 (3,94”) 1 and example fig. 7. 2.7.
Page 12
0,3 mt (12 inches) max 0,5 m 1 Separate flue kit code 8089909 2a 90° elbow MF 2b Isolated 90° elbows MF 3a Extension L. 1000 mm (39.4 inch) 3b Insulated extension L. 1000 mm (39.4 inch) 3c Extension L. 500 mm (19.7 inch) 4 Outlet terminal 5 Int.-est.
POSITIONING OF OUTLET 50 mm (2 in) from the outstide wall at buildings. Table 2 shows approximate, non- TERMINALS (fig. 11) least. binding minimum distances to be met for a building of the type shown in fig. 5. Please The outlet terminal must be flush with the Outlet terminals for forced draft systems refer to local codes for minimum clearan- wall and the inlet terminal must protrude...
Page 14
2.8.2 Instructions special stainless steel venting system for use with Category III appliances TERMINATION HOOD SVSHTX03 Z-FLEX recommends that an experienced should be enclosed below the roof line least one support collar at the base of professional who works with venting with a chase to limit condensation and the vertical run.
Page 15
Examine all components to insure that 1. Align pipes and push them together as in/lbs. gasket integrity has remained during ship- far as they will go (to indent or at least ping. Gaskets must be in the proper position 1.75 inches). NOTE: Some flue collars may require the or flue gases could leak resulting in carbon 2.
Page 16
Side wall venting installation 2. The system can now be assembled throu- every 12 inches (305 mm) to prevent (see figure 6/a below) gh the thimble (attach the termination collection of condensate at any location first - note “UP” arrow) and then back to in the assembly.
Page 17
Vertical venting the framed opening and secure with pipe. Seal as required using high tem- (see figure 6/b - 6/d) nails or screws as required. perature silicone. NOTE: The vent termination must be at 3. Refer to JOINT PROCEDURE (figure 6) 6.
Page 18
Above the roof system. cable with a minimum rated capacity of (see figure 6/c) 500 lbs (227 kgf) to each of the four 1. Install the Guy Band below the Rain Cap anchor holes. NOTE: When Z-Vent must be extended using the 10-24 screw and nut provi- 3.
Page 19
Existing masonry chimney up with opening in chimney. (A rope may 4. The rain cap may now be installed using (See figure 6/e) be used to facilitate lowering of pipe). the JOINT PROCEDURE (figure 6). NOTE: A masonry chimney flue may be used 2.
The thermostat or timer-thermostat, NOTE: The boiler must be connected with dangerous operation. recommended for better room tempera- an efficient grounding system. SIME shall After connecting all wires, verify proper ture control, must be dry contact. IMPORTANT: Before perfor- ming any kind of operation,...
Page 21
2.9.3 Wiring diagram 120V 60Hz CONNECTOR SPARE PART CODES: CN2 code 6299909 CN6 code 6299906 CN7 code 6299907 Ignition transformer Fuse (1.6 AT) 100°C (212°F) safety stat C.H. pump Water pressure switch EV1-2 Gas valve coil Flowmeter Smokes stat Time programmer Smoke pressure switch Divertor valve Modulator...
CHARACTERISTICS 3. 1 ELECTRONIC BOARD The electronic boards are manufactured in Bi-colour green led off if power is cut-off. compliance with the ANSI and Canadian Bi-colour orange led: C.H. sensor (SM) fault. directives. Green led flashing: fan/smoke pressure switch/smoke stat failure. They are supplied with 120V and, through a Orange flashes on water circulation.
ELECTRONIC IGNITION Ignition and flame detection is controlled by an electrode located on the burner. These guarantee maximum safety with interven- tion times, for accidental switching off or gas failure, of within one second. 3.3. 1 Operating cycle Rotate the rotary switch to summer or win- ter, the red led should light up.
the system, turn off the by-pass by turning the union to the vertical position (fig. 17/a). ELECTRICAL WIRING OF ZONE HEATING SYSTEMS By-pass off By-pass escluso When installing a system of this type, use a separate electrical line to which room ther- mostats with their local valves will be con- nected.
(4) supplied in the This operation must be performed by kit when replacing nozzles, even in bur- authorised personnel using original Sime ner units for which it is not specified. components. To convert from natural gas...
1. Close the gas cock. to the intake downstream of the gas mum pressure values correspond to 2. Disassemble the burner manifold (3). valve. the established values; correct the set- 3. Replace the main nozzles (6) supplied in Disconnect the valve VENT pressure test tings if necessary.
burner manifold unit . To clean the bur- ner, blow in a jet of air, so as to remove any dust particles that may have accu- Spia lampeggiante mulated. FLASHING 3. Clean the heat exchanger, removing any verde/arancio GREEN/ORANGE LED dust or residue from combustion.
vessel. 2. Check whether connection tubes of 6. Replace expansion vessel if faulty. Smell of unburnt gases. smoke pressure switch are obstructed 1. Check boiler is properly clean. and, if necessary, clean away impurities Radiators fail to heat up in winter. 2.
Page 29
Manuel de montage, d'utilisation et d'entretien FORMAT.zip of Gas-Fired Wall Hung Hot Water Boilers TABLES DES MATIÈRES AVERTISSEMENT: En ne suivant pas scrupu- DESCRIPTION DE LA CHAUDIÈRE leusement les informations contenues dans ce manuel vous risquez de provoquer une 1. 1...
Ce manuel donne les raccordements sont corrects, y 10. Le moteur doit informer l'utilisateur des instructions sur le FORMAT.zip 35 BF compris ceux du brûleur. sur le mode de fonctionnement de la à modulation et allumage électroniques, à...
Page 31
DISTANCES DES MATÉRIAUX Modèle 35 BF Unités Gaz naturel Propane COMBUSTIBLES : Bas: 0 mm (0 in.) Puissance nominale 39.2 37.3 Côtés: 0 mm (0 in.) But/h 133,800 127,300 Dos: 0 mm (0 in.) Devant: 0 mm (0 in.) Puissance minimale 15.7 17.
Page 32
LÉGENDES Ventilateur Echangeur principal Chambre de combustion Vanne du gaz Echangeur à plaque EAU SANITAIRE Vanne pressostatique Sonde chauffage (SM) Thermostat sécurité100°C 10 Purgeur d'air 11 Vase d'expansion 12 Soupape de sécurité 13 Vidage de la chaudière 14 Débitmètre d'eau 15 Thermohydromètre 16 Dérivation automatique 17 Filtre eau sanitaire...
INSTALLATION Le montage doit être conforme aux prescriptions mauvaise combustion et de la suie peut se for- 2.2.2 Syndicats de connexion de système de l'autorité compétente ou, en leur absence, au mer dans le brûleur, la chambre de combustion code national gaz naturel, au code ANSI ou le conduit d'évacuation.
Page 34
Les sections de la tuyauterie formant le système doit garantir une alimentation en gaz suffisante pour couvrir la demande maximum, en limitant la perte de pression entre le compteur de gaz et les appareils utilisés à un maximum de : 1.
1 mètres de long. Pour les 4. La distance entre la prise d'air et le tales doivent être soutenues tous les mètres (39 options d'évacuation C32 vous devez com- tuyau de fume ne doit pas dépasser TUYAUTERIE TYPIQUE “FORMAT.ZIP 35 BF” OFFRE D'EAU CHAUDE OFFRE...
Page 36
300 mm (12 in) 5. La perte de prévalence du tuyau des fumées ne doit pas dépasser 4,8 mm (0. 1 9 in) de la perte de prévalence de la prise. 6. Le terminal de sortie doit dépasser de 50 mm (2 in) du mur extérieur. Voir la fig.
Page 37
2.7. 1 Kit conduits d'évacuation séparés (fig. 8) 205 (8.07”) Le kit de conduits d'évacuation séparés code 100 (3,94”) 8089909 est équipé d'un diaphragme de prise que vous devez utiliser en suivant les indications de la figure 8/a, selon la perte de prévalence maximum autorisées dans les deux conduits d'évacuation.
Page 38
max 0,3 mt (12 in) max 0,5 m LEGENDE Kit conduits séparés cod. 8089909 2 a Coude à 90° MF 2 b Coude à 90° MF calorifugé 3 a Rallonge L. 1000 mm (39.4 in) 3 b Rallonge L. 1000 mm (39.4 in) calorifugé 3 c Rallonge L.
POSITIONNEMENT DES mm (2 in) au moins du mur extérieur. murs extérieurs d'immeubles. TERMINAUX DE SORTIE (fig. 11) Le Tableau 2 illustre les distances mini- Les terminaux de sortie des systèmes à mum appropriées, non obligatoires, sur les Le terminal de sortie doit dépasser de 50 tirage forcé...
Page 40
2.8.2 Instructions spéciales pour système dìéventage en acier inoxydable pour les Catégories d’Equipements III. LISTE DES PIECES DE RECHANGE COMPOSANT CAT. SYSTEM 3” COMPOSANT CAT. SYSTEM 3” 10 TUYAU SVEPWC0310 REGLAGE SOLIN SVSADJ03 8 TUYAU SVEPWC0308 RACCORD 4’’ A 3’’ SVSERWC0403 5 TUYAU SVEPWC0305...
Page 41
Procédure d’assemblage Les joints doivent être installés correctement 2. Serrer la vis du collier d’une torsion minimum (voir figure 6 ci-dessous) sinon le tuyau du gaz pourrait avoir des fuites de de 40in/lbs à un maximum de 50 in/lbs. monoxyde de carbone qui est un poison. La terminaison femelle de chaque composant NB: Pour certains colliers de tuyaux il peut être d’évacuation Z comprend un joint d’étanchéité...
Page 42
Installation évacuation sur mur latéraux travers les cosses, (fixer d’abord la terminai- mulation de condensation dans toute portion (voir fig. 6/a ci-dessous) son remarquer la flèche HAUT.) et ensuite de l’assemblage. Les agrafes ne doivent pas vers l’installation voir PROCEDURE D’AS- pénétrer les composants du système lors du 1.
Page 43
Evacuation verticale sions voulues. Insérer le support depuis der- (vour figure 6/b- 6/d) rière l’ouverture encadrée et fixer à l’aide de 6. Installer le support supérieur autour du tuyau clous ou de vis. et contre le collier de solin (fig. 6/b -6/d- N.B.
Page 44
AU-DESSUS DU TOIT un hauban pour tenir le système. vanisé d’une portée minimum de 500 lbs (voir figure 6/c) (227 kgf) à chacun des quatre trous 1. Installer le hauban au-dessous du cha- d’ancrage. NB: Lorsque l’évacuation Z doit être peau d’évacuation à...
Page 45
Cheminée en maçonnerie existante minée jusqu’à l’extrémité de l’ouverture de 4. On peut maintenant installer le chapeau (voir fig. 6/e) la cheminée (on peut utiliser une corde d’évacuation en suivant la PROCEDURE pour faciliter cette descente) D’ASSEMBLAGE (fig.6). N.B. Une cheminée d’évacuation en maçon- nerie peut être utilisée pour convoyer Z- 2.
CÂBLAGE ÉLECTRIQUE efficace. SIME décline toute responsabi- q q u u e e l l e e f f o o n n c c t t i i o o n n n n e e m m e e n n t t e e s s t t c c o o r r r r e e c c t t a a p p r r è è s s l l ' ' e e n n t t r r e e t t i i e e n n .
Page 48
CARACTERISTIQUES 3. 1 TABLEAU ÉLECTRONIQUE Diode bicolore verte éteinte: manque de tension. Les tableaux électroniques sont fabriqués Diode bicolore orange anomalie de la sonde de chauffage (SM). conformément aux Directives canadiennes Diode verte intermittente panne du ventilateur/ et ANSI. Ils sont alimentés en 120V à tra- pressostat fumées/intervention de aquastat de fumées.
ALLUMAGE ÉLECTRONIQUE L'allumage et la détection de flamme sont commandés par un électrode située dans le brûleur. Cela permet de garantir le maximum de sécurité avec des temps d'intervention infé- rieurs à la seconde en cas d'extinction acci- dentelle ou de panne de gaz. 3.3.
position verticale (fig. 17/a). CÂBLAGE ÉLECTRIQUE DES SYSTÈMES DE CHAUFFAGE DE ZONE Si vous installez un système de ce type, utili- By-pass désactivé By-pass escluso sez une ligne électrique sépar ée sur lesquels brancher les thermostats d'am- biance avec leur robinets locaux. Branchez les microinterrupteurs ou les contacts des relais sur les bornes 15 et 16 By-pass activé...
USE AND MAINTENANCE 4. 1 RÉGLAGE DE LA TEMPÉRATURE EAU CHAUDE SANITAIRE SIT 845 SIGMA HONEYWELL VK 4105M Le système muni de potentiomètre de réglage de la température de l' eau sanitai- re avec une plage de réglage comprise entre 30°C et 60°C (86-140 F) offre un double avantage: 1) La chaudière s'adapte parfaitement à...
à l'aide de flamme nue à proximité. pas réglée. composants Sime d'origine. 8. Mettez hors tension le modulateur et Pour passer du gaz naturel au GPL ou vice- laissez le robinet d'eau chaude ouvert. versa, procédez de la sorte (fig. 22): 4.4.
NETTOYAGE ET ENTRETIEN Nettoyez le générateur en procédant de la Spia lampeggiante sorte: FLASHING 1. Débranchez le cordon électrique de la verde/arancio GREEN/ORANGE LED chaudière et fermez le robinet de gaz. 2. Retirez le carter extérieur et la rampe de brûleurs. Pour nettoyer les brûleurs, soufflez de l'air pour éliminer la poussiè- 3.
Page 54
froide n'est pas trop élevé, respectez les 1. Vérifiez si la pression du gaz du brûleur est vitesse maxi. valeurs recommandées. correcte. 1. Vérifiez si le pressostat des fumées est en 3. Vérifiez si la soupape de sécurité est correc- 2.