acoustic signalling of the control unit (keyboard tones,
alarms, and diagnostics).
A list of the allowed regulation ranges for every single value
is given in the annex ' PARAMETERS '.
P5: RELAY LOGIC SELECTION
Using this parameter it is possible to reverse the output logic
from Normally Open (N.O.) to Normally Closed (N.C.) and
vice- versa. It is only possible to modify the output logic for
the relays actually active in the selected setup.
Value '1' for these parameters means that the output logic is
reset to the N.O. value (default).
The only output whose logic can be modified is OUT2 and it
is listed under the heading ' PARAMETERS '.
If the controller displays 'NONE' it means that 'OUT2' is not
provided for in the selected layout.
P6: INTEGRATION HOURS COUNTER
Using this parameter it is possible to display the actual number
of hours of the integrative source operation or reset it.
AFTER SELECTING PARAMETER P6 PRESS THE ' '
KEY.
THE DISPLAY SHOWS 'H' AND ACTUAL HOURS OF
ACTIVITY OF THE INTEGRATIVE SOURCE.
PRESS THE ' ' KEY , THE DISPLAY
SHOWS 'H' FLASHING.
PRESSING THE ' ' KEY RESETS THE COUNTER,
PRESSING THE ' esc ' AGAIN SHOWS THE CURRENT
RUNNING HOURS.
The counter recording the running hours of the integrative
source can handle values up to 9999. Once the maximum
value is reached the counter stops.
P7: LOADS WIRING TEST
This parameter allows to set the test of the loads wired to
the control unit as well as the wirings themselves.
The control unit tests the loads connected to it, according to
the selected diagram, by turning on all the available outputs
in sequence for 10 seconds each.
The number of times for which the entire test is repeated, in
50