Installation and operating manual
(PVI-3.8/4.6-I-OUTD Rev.: 1.5)
5.5.6.6

Date/Time

The time and date can be modified from this section, if necessary.
5.5.6.7

Language

It is possible to set one of the following languages: ENGLISH, GERMAN,
ITALIAN,FRENCH, SPANISH, CZECH.
5.5.6.8

START-UP Voltage

The start-up voltage can be adjusted (if they are configured independently) also
separately for both channels in order to tailor it to the needs of the system. The voltage
range is from 120V to 350V. The default setting for AURORA is 200V. This
parameter may be varied by using the display keys.
5.5.6.9

Autotest Operation

In accordance with the "guide for connection to the ENEL power supply distribution
grid", the autotest can be launched through the menu on the display or by using an
RS485/USB converter and the AURORA Communicator software (see paragraph 5.6
for further details).
The following conditions are necessary for the Autotest to be performed:
You must have set the ENEL grid standard.
-
The inverter must be connected to the grid in a way that allows simulating a
-
disconnection condition.
Do not carry out any operation during the test execution phase.
-
Check that the device is connected to the grid in a stable way
-
Follow the procedure below in order to perform Autotest:
Access the menu SETTINGS > Autotest
-
In the section of the menu dedicated to the Autotest, the type of test that the
-
device must start may be selected from the following:
Time 14:21
Date 17 May 2006
English
Italian
Set
VStart
200V
Page 69 of 95