6.3
minimum clearance to combustibles
Framed Enclosure
Rear
Sides
Ceiling
(enclosure)
Ceiling
(in front of appliance)
Chimney
Hot air Gravity Ductwork Insulation
Solid Pack Chimney
Ceiling
(enclosure)
Air Cooled
Ceiling
(enclosure)
6.4
minimum enclosure clearances
Shown with air intake liner coiled to create a cold trap.
OR
A minimum of 6" (152mm) is required to combustibles from
the side of the appliance. This is only if the intake liner is
routed below the 2" (51mm) projection of the outer casing
of the appliance. If the intake liner is routed vertically along
the side of the appliance then a spacing of 7" (178mm) is
required.
When framing in appliance, allow for fi nishing material thickness.
- 0" (0mm) to stand-offs (rear)
- 6" (152mm) to sides
- 120" (304.8cm) from the base of the appliance (unless shielded
with metal studs and cement board)
- 84" (213.4cm) from the base of the appliance
- 2" (51mm) (follow manufacturers instructions)
- 1" (25mm)
- 120" (304.8cm) from the base of the appliance (unless shielded
with metal studs and cement board).
- 84" (213.4cm) from the base of the appliance
framing
2 layers of 1/2" (13mm)
cement board needed to fi ll
gap A.
23
W415-1501 / G / 05.10.22
EN