5.1
MINIMUM CLEARANCE TO COMBUSTIBLES
Minimum clearance to combustible construction from appliance and vent surfaces:
Combustible Framing:
-
-
-
Combustible Finishing:
-
-
-
Rear Vent:
-
-
Top Vent:
-
-
* HORIZONTAL VENT SECTIONS - A minimum clearance of 1" (25mm) at the bottom and sides and 2" (51mm)
at the top of the vent pipe in all horizontal runs to combustibles is required except for clearances in appliance
enclosures, see "MINIMUM ENCLOSURE CLEARANCES" section. Use fi restop spacer W010-1777 (supplied).
* VERTICAL VENT SECTIONS - A minimum of 1" (25mm) all around the vent pipe on all vertical runs to
combustibles is required. Use fi restop spacer W500-0096 (not supplied).
DO NOT BUILD INTO THIS AREA - IT MUST BE LEFT CLEAR TO PROVIDE ADEQUATE CLEARANCE
FOR THE VENT. IN THIS 14" (356MM) WIDE AREA CENTRED ALONG THE FRONT OF THE APPLIANCE,
*KEEP FACING MATERIAL 1/4"(6mm) FROM SIDE OF
UNIT TO ACHIEVE OPENING WIDTH OF 20 1/4" (514mm).
NOTE: MUST BE MAINTAINED FOR THE FACING KIT
TO COVER THE OPENING
0" to stand-offs
1" (25mm) to bottom and sides of the vent pipe*
2" (51mm) to top of the vent pipe*
0" to rear
0" to front face top and sides
13" (330mm) recessed depth
39 1/8" (994mm) to enclosure top from base of the unit
45 1/8" (1146mm) to ceiling from base of the unit
53 1/8" (1349mm) to enclosure top from base of the unit
53 1/8" (1349mm) to ceiling from base of the unit
NO COMBUSTIBLES ARE ALLOWED.
NON-COMBUSTIBLE
BOARD REQUIRED
3"
76mm
MINIMUM
COMBUSTIBLE
MATERIAL
FINISHING
*
MATERIAL
OPENING
HEIGHT
MUST BE
34 1/8"
867mm
3"
76mm
MINIMUM
WARNING
!
1 1/2"
38mm
MAXIMUM
14"
356mm
MINIMUM
1 1/2"
38mm
MAXIMUM
* 1/4 "
6mm
13 1/4"
337mm
W415-1351 / 08.29.14
33
EN