Heat recovery unit bypass
---%
Control (-) :--- (+) :---
2.5.3 Calculated setpoints
wc1
Calculated
--.-°c
2.5.4 Calculated demand
c1
Cooling demand
---.-%
Heating demand
---.-%
Dehumid. demand
---.-%
Humid. demand
---.-%
Cooling block
---
Heating block
----
dc2
Annual program
Heating oper.
Mid-season oper.
Heating oper. valid.
---
Cooling oper. valid.
----
2.5.5 Counters
Counters
tt1
Supply air fan
-----h
reset -
Heat exchanger bypass damper opening valve
Heat recovery unit bypass damper (-) closing (+) opening control state : Off or On
-
Control setpoint calculated for the Supply air temperature when the regulated temperature is
Return or Ambient in "Precision" mode
-
Calculated cooling demand calculation value
Calculated heating demand calculation value
Dehumidification demand calculation value
Calculated humidification demand calculation value
Information on whether the cooling operation is blocked (no, yes)
Information on whether the heating operation is blocked (no, yes)
State (inactive, active) of the heating operation annual programming
---
---
State (inactive, active) of the mid-season operation annual programming
Validation (no, yes) of heating operation by annual programming (heating and mid-season)
Validation (no, yes) of cooling operation by annual programming (heating and mid-season)
Supply air fan runtime counter reset and time