p29
Mid-season oper. period
(1)Validation:
----
(1)Start date:
DD/MM
(1)End date:
DD/MM
(2)Validation:
----
(2)Start date:
DD/MM
(2)End date:
DD/MM
Selection: Without, With
DD: 1 to 31
MM: 1 to 12
Calibration
ca1
Return air
00.0°c
Supply air
00.0°c
Fresh air
00.0°c
Water system
00.0°c
Calibration
ca2
Fresh air sensor
Filter sensors 1
Filter sensors 2
Filter sensors 3
Humidity
00.0%
Air quality
000ppm
Recup. sensor
Heat recovery, filter 1, 2, 3 clogging sensor type : 0-1000Pa 10V, Ratio (0-1000Pa), 0-100Pa 10V, 0-250Pa 10V, 0-500Pa 10V,
0-750Pa 10V.
Calibration
cam
Calibration probes of
Pressure
NO-
supply
return
Fan
---- Pa
---- Pa
Filter
---- Pa
---- Pa
Add. Filter
---- Pa
Recuperator
---- Pa
Input direction
se1
Heat pump control
NC
S.A fan control
NC-
Frost protection thermostat
NO
Damper end of
NC
travel
Fire sensor
NC
Elec heater safety
NC
Remote control
NC
Level 2 access
Validation of mid-season operation period 1
Start date for mid-season operation period 1
End date for mid-season operation period 1
Validation of mid-season operation period 2
Start date for mid-season operation period 2
End date for mid-season operation period 2
Level 3 access
Calibration of the regulated temperature sensor (return or room)
Calibration of the supply air temperature sensor
Calibration of the fresh air temperature sensor
Calibration of network water temperature sensor
Level 3 access
Selection of the presence of a fresh air temperature sensor (Display only)
-
Filter 1 clogging sensor type
-
Filter 2 clogging sensor type
Filter 3 clogging sensor type
Humidity sensor calibration
Calibration of air quality sensor
Heat recovery clogging sensor type
Level 3 Access Press the prog button from screen ca1 or ca2
Manual calibration of pressure sensors. Warning: the fans must be completely stopped before
using this function.
Fan pressure sensor calibration (supply and extraction)
Filter clogging sensor calibration (supply and extraction)
Filter clogging sensor calibration (supplementary filter)
Heat recovery clogging sensor calibration
Level 3 access
Direction of the heat pump control information during operation
Direction of the supply air fan sensor information during operation
Direction of the frost protection thermostat control information during operation
Direction of the damper end of travel control information in the open position
Direction of the fire sensor control information during operation
Direction of the electric heater control information during operation
Direction of the control information for the remote control when "On"
EN - 28