p4
Regulated T°
--------
Air quality
-------
M factor
01.0
Quality band
100
Adiab. cooling On
0.5
Supply air
p5
High T shift
05.0
Low T shift
-05.0
Shutdown valve 1 open
000%
Shutdown valve 2 open
000%
Return air
p6
High T shift
05.0
Low T shift
-05.0
Humidity
p7
High H shift
20.0
Low H shift
-20.0
Sensor on connector:
-------
Sensor on connector: J6-B7, J6-B8
p14
Fan
Supply air
Band
0595.0
I T
0004s
D T
0001s
Return air
Band
0595.0
I T
0004s
D T
0001s
p15
Duct
Band
0595.0
I T
0004s
D T
001s
Level 2 access
Regulated T°: Supply, Return or Ambient air
Air quality: Without, 0-5V, 0-10V (not available if the fans are monitored based on
constant Supply air duct pressure)
Proportionality factor value for Supply air duct flow rate and pressure control
Air quality regulation proportional band
Adiabatic cooling authorisation shift in relation to the set T° setpoint in cooling mode
Level 2 access
High supply air temperature threshold shift
Low supply air temperature threshold shift
Opening value for the valve for heating coil 1 when the supply air ventilation is stopped
Opening value for the valve for heating coil 2 when the supply air ventilation is stopped
Level 2 access
High return (or ambient) air temperature threshold shift
Low return (or ambient) air temperature threshold shift
Level 2 access
High humidity threshold shift
Low humidity threshold shift
Level 3 access
Level 3 access
Supply air fan flow rate control proportional band
Integral time and derivative time for supply air fan flow rate control
Return air fan flow rate control proportional band
Integral time and derivative time for return air fan flow rate control
Level 3 access
Duct pressure control proportional band
Integral time and derivative time for duct pressure
EN - 25