Comfort
w4
Return air
Cooling 25.0°C
Eco 27.0°C
Return air
Heating 23.0°C
Eco 18.0°C
Deadband
Comfort
w5
Supply air
Cooling 16.0°C
Eco 18.0°C
Supply air
Heating 26.0°C
Eco 24.0°C
U:01
w6
Frost protection
17.0°C
w7
Night cooling
17.0°C
Supply
020000m³/h
Return
020000m³/h
w8
Electric heater
Off
On
Stage 1
000.0%
033.3%
Stage 2
033.3%
066.6%
Stage 3
066.6%
100.0%
w9
Humidity
50.0%rH
Indication of the operating mode for T° control in "Energy optimisation" mode Level 1 Access
Monitored Comfort Cooling (Return, Ambient or Supply air) temperature control setpoint (0 to 50.0°C)
Monitored Eco Cooling (Return, Ambient or Supply air) temperature control setpoint (0 to 50.0°C)
Monitored Comfort Cooling (Return, Ambient or Supply air) temperature control setpoint (0 to 50.0°C)
Monitored Eco Cooling (Return, Ambient or Supply air) temperature control setpoint (0 to 50.0°C)
Indication of the control state for the monitored temperature
Indication of the operating mode for T° control in "Energy optimisation" mode Level 1 Access
Cooling Comfort monitored temperature control setpoint (Regulated T° ≠ Supply air) (0 to 50.0°C)
Cooling Eco monitored temperature control setpoint (Regulated T° ≠ Supply air) (0 to 50.0°C)
Heating Comfort Supply air temperature control setpoint (Regulated T° ≠ Supply air) (0 to 50.0°C)
Heating Eco Supply air temperature control setpoint (Regulated T° ≠ Supply air) (0 to 50.0°C)
Level 2 access
Unit reactivation setpoint in "Standby" mode when there is an ambient temperature sensor
Level 2 access
Regulation setpoint in "Night cooling" mode
Supply airflow setpoint during night cooling
Extract airflow setpoint during night cooling
Level 3 access
Stage 1 on and off setpoint for the electric heater
Stage 2 on and off setpoint for the electric heater
Stage 3 on and off setpoint for the electric heater
Level 1 access
Control setpoint for the return air humidity
EN - 20