1.5.8 Temperature control
The set temperature may be:
- the return air temperature
- the room temperature
- the supply air temperature
Two temperature control schemes are available:
- "Precision" mode, where a low deviation from the reference temperature is requested.
- "Energy optimisation" mode, where the key factor is the cost of energy.
"Precision" mode:
In this case, the regulated temperature is the room or return air temperature and the difference between this temperature and the
setpoint enables the setpoint used as the basis for controlling the supply air temperature to be calculated
Calculated Supply air T°
setpoint
Low threshold
alarm
upper limit
Setpoint
lower limit
Setpoint -5°C
250Pa
Dirty
filter
detection threshold
X1
Comfort: -5°C
Eco: -7°C
Setpoint
Comfort: 20°C
Eco: 16°C
EN - 7
400Pa
Clogged
filter
detection threshold
High threshold
alarm
Setpoint +5°C
X2
Comfort: 5°C
Eco: 7°C
Pa
Filter pressure
drop
EN
°C
Return T°
Room T°