1.5.17 Adiabatic cooling
The aim is to introduce fresh air into the room in question without using the unit's cooling coil during a cooling request.
The action will be to cool the return air flow, which is hot, from a dual-flow unit equipped with a rotary or plate heat exchanger,
by increasing its humidity level via a trickle humidifier.
This will allow the fresh air going through the heat recovery unit to be refreshed.
This humidifier will be controlled by the relay output NO17 if:
- The function is requested
- The unit comprises a heat recovery unit
- The unit is operating
- There is a supply air cooling requirement
- The fresh air temperature is greater than the supply air cooling setpoint.
1.5.18 The fault relays
One relay per fault summary level is provided:
- "Maintenance" fault summary
- "Danger" fault summary
"Maintenance" faults are alarms which only send information to notify the operator. They can be validated by pressing the key for
3 seconds
if they have disappeared.
The "Danger" faults, which are of a higher level, are alarms which send information to notify the operator, but also start a process
to secure the unit. They can be validated by pressing and holding the
button for 3 seconds if they are no longer present, and once the unit is switched Off.