Use "Choose XML file " to open the required configuration XML file
Click on "Download data" and confirm the confirmation prompt .
Wait until the message "Memory Access closed successfully" is displayed. During the loading phase indicated by the control lines
passing under ETS5 and the flashing green LED on the card, no other operations can be performed. The charging time can vary
depending on the size of the XML file and network traffic ; to a maximum file size , this time can be 2 minutes.
In extreme cases , that is to say a high traffic and large XML files, the bus can disconnect and ETS5 indicate an error. In this case,
simply repeat loading.
NOTE : This procedure is specific to the KNX card and is the only configuration operation , in addition to the allocation of the
address, permitted by ETS5 program.
KNX variables loaded with this plug-in does not appear in the Group Objects tab. To check and / or edit your group addresses you
must open your xml file from KSET , and once you are done, reload the plugin via the ETS .
Our controller has no configuration parameters accessible in KNX . They are only accessible from the HMI .
EN - 62