On request, the "Air_Technologies_110905.XIF" file is available.
5.4.1 LON scope of supply
Recap of on-site LON tasks by CIAT/Installer/Integrator for commissioning:
Task
Commissioning service
Supply of .XIF integration file
Installation of units equipped with LON controller
Addressing and configuration of LON network
Definition of master/slave zones
Definition of setpoints and time programs
5.4.2 Digital variables
Type
Index
DGT
1
DGT
1
DGT
--
DGT
--
NV name
SNVT
nvi_GTC_OnOff
95
nvo_GTC_OnOff
95
nvo_entree_dig_1
83
nvo_sortie_dig_1
83
CIAT
Integrator
Direction
input
Unit On/Off command via CMS
output
Unit On/Off control return via CMS
output
State of digital inputs
bit 0
Not used
bit 1
Heat pump unit control state
bit 2
Supply air fan control state
bit 3
Frost protection thermostat control state
bit 4
Damper end of travel state
bit 5
Fire sensor state
bit 6
Electric heater thermostat sensor input
bit 7
Remote control state
bit 8
Return air fan control state
Burner control state
bit 9
bit 10
Burner fault state
bit 11
Overheating fault state
bit 12
State control or rotary heat recovery pump
Brine recovery
output
State of digital outputs
bit 0
Danger fault output
bit 1
Maintenance fault output
bit 2
Supply air fan control
bit 3
Return air fan control
bit 4
Damper control
bit 5
Electric heater stage 1 control
bit 6
Electric heater stage 2 control
bit 7
Electric heater stage 3 control
bit 8
Burner commissioning control
bit 9
Burner stage 1 control
bit 10
Burner stage 2 control
bit 11
Motor control of rotary heat recovery constant speed pump or
brine recoveryl
EN - 51
Installer
Description
EN

Hide quick links:

Publicité

Chapitres

Table des Matières
loading

Table des Matières