p16
Supply air limits
Shift X1
-5.0°C
Eco
-7.0°c
Shift X2
5.0°c
Eco
7.0°c
Prioritising
p18
heat generators
Start
End
Wheel
---.-
---.-
Burner
---.-
---.-
Coil 1
---.-
---.-
Coil 2
---.-
---.-
E heater
---.-
---.-
Prioritising
p19
Stage distribution
electric heater
Stage 2
033.3%
Stage 3
066.6%
Air quality
p20
Sensor on connector:
------
Sensor on connector: J6-B6, J6-B7
p21
Heat recovery unit bypass
Neutral
0000
Band
005.0
I T
0004s
D T
0001s
p22
recuperator
Minimum distance
5.0°c
Level 3 access
Supply air T° setpoint calculation parameters (See Fig., page 9)
X1 shift value for the formula for calculating the supply air temperature Comfort setpoint
X1 shift value for the formula for calculating the supply air temperature Eco setpoint
X2 shift value for the formula for calculating the supply air temperature Comfort setpoint
X2 shift value for the formula for calculating the supply air temperature Eco setpoint
Level 3 access
Rotary heat exchanger actuation start and end setpoint value
Burner actuation start and end setpoint value
Coil 1 actuation start and end setpoint value
Coil 2 actuation start and end setpoint value
Electric heater actuation start and end setpoint value
Level 3 access
Setpoint value for the electric heater stage 2 actuation start
Setpoint value for the electric heater stage 3 actuation start
Level 3 access
Level 3 access
PID deadband value for the plate recovery unit bypass control
PID proportional band value for the plate recovery unit bypass control
PID integral time and derivative time for the plate recovery unit bypass control
Level 2 access
Value of the difference between T ° mini recovery (or room ) and T ° new authorization for air recovery
EN - 26