5.3.4 Variables
5.3.4.1 Orders
Register hex.
Register
no.
decimal no.
Dampers accessible in read-only mode (functions 3 or 4) and write mode (functions 6 for char or 16)
0x0190
400
0x0191
401
0x0192
402
0x0193
403
0x0195
405
0x0196
406
0x019A
410
0x019B
411
0x019C
412
0x019D
413
0x1A1
417
0x1A2
418
0x1A6
422
0x1A7
423
0x1A8
424
0x1A9
425
0x1AC
428
0x1AD
429
0x1AE
430
0x1AF
431
0x1B4
436
0x1B9
441
0x1BD
445
0x1BE
446
0x1BF
447
0x1C0
448
0x1C1
449
0x1C2
450
0x1C3
451
0x1C4
452
0x1C5
453
0x1C9
457
0x1CF
463
0x1D0
464
0x1D1
465
0x1D4
468
0x1D5
469
0x1D6
470
0x1D9
473
0x1DA
474
0x1E5
485
0x1E6
486
0x1E7
487
0x1EB
491
0x1EC
492
Description
Supply air fan flow rate setpoint value
Return air fan flow rate setpoint value
Supply air fan reduced flow rate setpoint value during a time
program
Return air fan ECO flow rate setpoint value during a time
program
Supply air duct pressure setpoint value
Supply air duct Eco pressure setpoint value during a time
program
Comfort heating regulated temperature setpoint value
Eco heating regulated temperature setpoint value during a
time program
Supply air temperature maximum limit value
Supply air temperature minimum limit value
Air quality regulation setpoint
Supply air fan maximum flow rate value for air quality
regulation
Cooling Comfort regulated temperature setpoint
Cooling Eco regulated temperature setpoint
Heating Comfort regulated temperature setpoint
Heating Eco regulated temperature setpoint
Cooling Comfort supply air temperature setpoint
Cooling Eco supply air temperature setpoint
Heating Comfort supply air temperature setpoint
Heating Eco supply air temperature setpoint
Frost protection setpoint value when the unit is in Standby
during a time program
Regulation setpoint in "Night cooling" mode
Stage 1 and off setpoint value for the electric heater
Stage 1 on setpoint value for the electric heater
Stage 2 off setpoint value for the electric heater
Stage 2 on setpoint value for the electric heater
Stage 3 and off setpoint value for the electric heater
Stage 3 on setpoint value for the electric heater
Set humidity setpoint
Free Cooling authorisation limit setpoint value in relation to the
fresh air temperature
Value of the minimum % of fresh air during Free cooling
management
Heat recovery unit bypass control setpoint value
Low threshold for supply air flow presence fault
High threshold for supply air filter 1 fouled fault
High threshold for supply air filter 1 blocked fault
Low threshold for return air flow presence fault
High threshold for return air filter 2 fouled fault
High threshold for return air filter 2 fouled fault
High threshold for additional filter 3 fouled fault
High threshold for additional filter 3 blocked fault
Changeover limit setpoint value in Heating mode and water
return temperature
Changeover limit setpoint value in Cooling mode and water
return temperature
Value for the water return temperature control proportional
band
Duct pressure sensor fault low threshold
Duct pressure sensor fault high threshold
Format
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
EN - 47
Type
Adjustable values
Read/Write
m3/h /10
Read/Write
m3/h /10
Read/Write
m3/h /10
Read/Write
m3/h /10
Read/Write
Pa
Read/Write
Pa
Read/Write
°C x10
Read/Write
°C x10
Read/Write
°C x10
Read/Write
°C x10
Read-only/Write
ppm
Read/Write
m3/h /10
Read/Write
°C x10
Read/Write
°C x10
Read/Write
°C x10
Read/Write
°C x10
Read/Write
°C x10
Read/Write
°C x10
Read/Write
°C x10
Read/Write
°C x10
Read/Write
°C x10
Read/Write
°C x10
Read/Write
%
Read/Write
%
Read/Write
%
Read/Write
%
Read/Write
%
Read/Write
%
Read/Write
%rH
Read/Write
°C x10
Read/Write
%
Read/Write
Pa
Read/Write
Pa
Read/Write
Pa
Read/Write
Pa
Read/Write
Pa
Read/Write
Pa
Read/Write
Pa
Read/Write
Pa
Read/Write
Pa
Read/Write
°C x10
Read/Write
°C x10
Read/Write
°C x10
Read/Write
Pa
Read/Write
Pa
EN