CIAT AirControl CTA Manuel De Régulation page 87

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

w10
Free Cooling
17.0°C
Fresh air min.
000%
w11
Heat recovery unit
fouling level
0250Pa
w13
Filter 1 Supply air
Flow presence
0010Pa
Filter dirty
0250Pa
Filter blocked
0400Pa
w14
Filter 2 Return air
Flow presence
0010Pa
Filter dirty
0250Pa
Filter blocked
0400Pa
w15
Filter 3 Supplement
Filter dirty
0250Pa
Filter blocked
0400Pa
w17
Changeover
Heating
40.0°C
Cooling
10.0°C
Limitation band
02.0°C
U:01
w18
Duct pressure
sensor check
Low threshold
10Pa
High threshold
900Pa
Outdoor temperature limit value for authorisation of Free Cooling (Level 3 Access)
Fresh air minimum value (Level 2 Access)
Level 3 access
Plate recovery unit frost saturation level detection setpoint or rotary heat recovery unit fouling detection threshold
Level 2 access
Supply air flow presence detection setpoint
Dirty supply air filter 1 saturation level detection setpoint
Blocked supply air filter 1 saturation level detection setpoint
Level 2 access
Return air flow presence detection setpoint
Dirty return air filter 2 saturation level detection setpoint
Blocked return air filter 2 saturation level detection setpoint
Level 2 access
Dirty additional filter 3 saturation level detection setpoint
Blocked additional filter 3 saturation level detection setpoint
Level 3 access
Value for the changeover limit setpoint in Heating mode and water return temperature
Value for the changeover limit setpoint value in Cooling mode and water return temperature
Value for the water return temperature control proportional band
Level 3 access
Intake duct pressure low threshold
Intake duct pressure high threshold
EN - 21
EN