Access to the following group of screens via the Prg button is protected by level 3 access
2.9 Communication menu
SUPERVISION
g1
Protocol
---------
Speed
------ Bauds
Address
------
Unit control
-----
pLAN NETWORK
pL1
Controller address
01
When the system starts up, the pLAN network may encounter a number of problems (card fault and terminal start-up) caused by
incorrect connections or a wrong address. The state of the pLAN network can be displayed in real time on this special mask in
order to identify which devices (controller or terminal) are correctly connected and addressed.
Network addresses 1 to 32 are displayed. The small rectangles
controllers.
If the symbols flash, the pLAN may be unstable or, more likely, two components share the same address.
The example indicates that the network is formed of 1 controller with the address 1 and 1 terminal with the address 17.
Annual2
Period
00:00 → 00:00
State:
----------------------
Start date:
DD//MM
End date:
DD//MM
Selection of the state during this period:
DD: day (1 to 31)
MM: month (1 to 12
Level 3 access
Choice of the communication protocol with the CMS (CAREL, LON, MODBUS RTU, KNX, WEB, MODBUS TCP)
Selection of the speed of communication with the CMS (4800 mandatory for LonWorks)
Address of the controller on the network for communication with the CMS (001 mandatory for LonWorks)
Selection of the On/Off control via the CMS
Address of the controller on the pLAN communication network to the user terminal
pLAN network state
Annual3
Period
00:00 → 00:00
State:
----------------------
Start date:
DD//MM
End date:
DD//MM
Inactive
Reduced T°
Normal T°
Min flow rate
Nominal flow rate
Min. pressure
Nominal pressure
Stand-by
Night Cooling
represent the terminals and the large rectangles
EN - 36
Annual4
Period
00:00 → 00:00
State:
----------------------
Start date:
DD//MM
End date:
DD//MM
, the