Configuration
c7
Heat pump unit
-----
Heat pump unit: Without, With

2.4 Settings parameters menu

Language
----------
t0
Setting
the clock
Time
-- / --
Date
--/--/--
Supply air
p1
Neutral cooling
00.0
Cooling band
0005.0
I T
0150s
D T
0000s
Neutral heating
00.0
Heating band
0005.0
I T
0150s
D T
0000s
Return air
p2
Differential
Cooling
Heating
0.0
0.0
p3
Test
--------
Mixing damper
-------
Fire
-------
Test: Without, Flow rate (Constant flow and independent setpoints) or Pressure (Constant supply air duct pressure and identical
fan speeds)
Mixing damper: Without, With
Fire: Without, With
Level 3 access
lg
Level 1 access
Controller language selection (French or English)
Level 1 access
Clock time correction value
Clock date correction value
Level 2 access
Deadband value for intake temperature control in cooling mode
Proportional band for intake temperature control in cooling mode
Integral time and derivative time for intake temperature control in cooling mode
Deadband value for intake temperature control in heating mode
Proportional band for intake temperature control in heating mode
Integral time and derivative time for intake temperature control in heating mode
Level 2 access
Value for the Return or Ambient air temperature control differentials
In cooling mode
Level 2 access
In heating mode
EN - 24