1.6 Controller inputs and outputs
G 24Vac
G0
Shared
Connector J2
B1
Fan flow rate or supply air duct pressure sensor (Option)
B2
Return air fan flow rate sensor (Option)
B3
Pressure sensor for presence of air flow and return air filter 1 fouling
GND
Shared
+VDC
Power supply for enabled sensors
Connector J3
B4
Return air or ambient temperature sensor (Option)
BC4
Shared for B4
B5
Supply air temperature sensor
BC5
Shared for B5
Connector J4
VG
24Vac
VG0
Shared
Y1
Water coil no. 1 valve control (heating, cooling or mixed) (Option)
Y2
Water coil no. 2 valve control (heating or cooling) (Option)
Y3
Supply air fan variable frequency drive control (Option)
Y4
Return air fan variable frequency drive control (Option)
Connector J5
ID1
Bypass or choice of heating coil function (Option)
ID2
Heat pump unit control (Option)
ID3
Supply air fan monitoring
ID4
Frost protection thermostat (Option)
ID5
Damper limit switch (Option)
ID6
Fire sensor (Option)
ID7
Monitoring of electric heater overheating thermostat (Option)
ID8
Remote control
IDC1
Shared
Connector J6
B6
Pressure sensor for presence of air flow and return air filter 2 or CO2 air quality filter fouling (Option)
B7
Pressure sensor for additional filter 3 or CO2 air quality sensor or return or ambient air humidity sensor fouling (Option)
B8
Pressure sensor for heat recovery unit or return or ambient air humidity sensor fouling (Option)
GND
Shared
Connector J7
ID9
Return air fan monitoring (option)
ID10
Switch S1 (Option)
ID11
Burner fault (Option)
ID12
Superheating thermostat (Option)
IDC9
Shared
Connector J8
ID13
Control of rotary heat recovery or the brine pump (optional)
IDC13
Shared
ID14
Humidifier monitoring (Option)
Connector J12
C1
Shared
NO1
Supply air fan control
NO2
Return air fan control (Option)
NO3
Control of damper (frost protection or insulation) (Option)
C1
Shared
EN - 16