NOTE: To gain access to trimmers (6) and (10),
slide off the central heating potentiometer knob.
3.2
TEMPERATURE SENSOR
AND WATER PRESSURE
TRANSDUCER
Antifreeze system made up of the NTC hea-
ting sensor that activates when the water
temperature reaches 6°C (43 °F).
Tables 4 - 4/a show the resistance values
(Ω) that are obtained on the sensor as the
temperature varies and the transducer
values obtained as the pressure varies.
When sensor (SM) is interrupted, neither
of the boiler's heating services will func-
tion. With D.H.W. sensor (SB) interrupted,
the boiler will only work in heating mode.
TABLE 4 (Sensors)
Temperature (°C/°F)
Resistance (Ω)
20/68
12.090
30/86
8.313
40/104
5.828
50/122
4. 1 61
60/140
3.021
70/158
2.229
80/176
1.669
10
11
9
TABLE 4/a (Transducer)
Pressure
(bar/psi)
0/0
0,5/7
1/14.5
1,5/22
2/29
2,5/36
3/43
3,5/51
3.3

ELECTRONIC IGNITION

Ignition and flame detection is controlled
by two electrodes located on the burner.
These guarantee maximum safety with
intervention times, for accidental swit-
ching off or gas failure, of within one
second.
3.3. 1

Operating cycle

Rotate the selector knob to summer or win-
ter, and verify that green led (
6
7
KEY
8
1 Ignition electrode earth faston
3 Fuse (1,6 AT)
5 "ANN. RIT." connector
6
6 "POT. ACC." trimmer
7 Conector "MET-GPL"
8 D.H.W. potentiometer
9 Detector electrode faston
13
10 "POT. RISC." trimmer
11 C.H. potentiometer
12 Selector REMOTE/OFF/
/SUMMER/WINTER/RESET

13 DIP SWITCH

14 Connector "Modureg Sel."
15 Connector "Albatros"
confirm the presence of voltage.
The boiler is now ready to start working
Resistance (Ω)
upon demand for heating or drawing off
mín
máx
of D.H.W.; a discharge current is sent to
297
320
the ignition electrode through the pro-
260
269
grammer, and the gas valve opens at the
222
228
same time.
195
200
The burner must be ignited within 10
167
173
seconds. However, it is possible for ignition
137
143
failures to occur, with consequent activa-
108
113
tion of signal indicating that the control box
90
94
has "locked out".
– Gas failure
The control box runs through the cycle
normally sending electric power to the
ignition electrode. The electrode conti-
nues spark discharge for a maximum of
10 sec.If the burner does not light, the
lock-out indicator will light up.
This may occur upon first ignition or
after long periods of boiler lay-off when
there is air in the pipes. It may be caused
by the gas cock being closed or by one of
the valve coils having a break in the win-
) lights up to
ding, so that the valve cannot open.
10
Fig. 20
ENG