O1: Setting Output 1 Function; O2: Setting Output 2 Function; Rf: Fault And Warning Reset; Pw: Change Password - DAB e.sybox Instructions Pour L'installation Et L'entretien

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 112
GB
ENGLISH
Factory configurations of the outputs
Uscita
OUT 1
OUT 2
Table 20: Factory configurations of the outputs

7.6.17 - O1: Setting output 1 function

Output 1 communicates an active alarm (it indicates that a system block has
occurred). The output allows the use of a normally open clean contact.
The values and functions indicated in Table 21 are associated with the param-
eter O1.

7.6.18 - O2: Setting output 2 function

Output 2 communicates the motor running status. The output allows the
use of a normally open clean contact.
The values and functions indicated in Table 21 are associated with the
parameter O2.
Configuration of the functions associated with the outputs
OUT1
Output confi-
Activation
Output contact
guration
condition
No associated
Contact always
0
function
No associated
Contact always
1
function
Presence
In the case of
2
of blocking
blocking errors the
errors
contact closes
98
Value
2 (fault NO closes)
2 (Pump running NO closes)
OUT2
Activation
Output contact
status
condition
status
No associated
Contact always
open
function
open
No associated
Contact always
closed
function
closed
Output activa-
When the motor is
tion in case of
running the contact
blocking errors
closes
Presence
In the case of
3
of blocking
blocking errors the
errors
contact opens
Table 21: Configuration of the outputs

7.6.19 - RF: Fault and warning reset

Holding down the + and – keys together for at least 2 seconds deletes
the history of faults and warnings. The number of faults present in the log
is indicated under the symbol RF (max 64).
The log can be viewed from the MONITOR menu on page FF.

7.6.20 - PW: Change password

The device has a password-enabled protection system. If a password is
set, the parameters of the device will be accessible and visible but it will
not be possible to change them.
When the password (PW) is "0" all the parameters are unlocked and can
be edited.
When a password is used (value of PW different from 0) all modifications
are blocked and "XXXX" is displayed on the page PW.
If the password is set it allows to navigate through all the pages, but at
any attempt to edit a parameter a pop-up appears, asking you to type in
the password. When the correct password is typed in the parameters are
unlocked and can be edited for 10' after the last key is pressed.
If you want to cancel the password timer, just go to page PW and hold
down + and – together for 2".
When the correct password is typed in a padlock is shown opening, while
if the wrong password is given a flashing padlock appears.
If the wrong password is typed in more than 10 times the same wrong
password padlock appears with inverted colours and no password can
be accepted until the appliance has been switched off and on again. After
resetting the factory values the password is set back at "0".
Each change of the password takes effect when Mode or Set is pressed
Output activa-
When the motor is
tion in case of
running the contact
blocking errors
opens

Publicité

Table des Matières
loading

Table des Matières