5.3 Speed Settings with Timers
SPEED WITH TIMERS
This menu items allows you to view and change the parameters associated with the speeds from 5 to 8 managed by
the timers.
5.4 Setting the speeds with remote control
EXTERNAL SPEEDS
This menu items allows you to view and change the parameters associated with the speeds X1-X4 that are activated
by an external digital signal.
5.5 Quick Clean speed settings
QUICK CLEAN
The "QuickClean" key allows you to perform a rapid wash of the system or fast recirculation, for example by cleaning,
suction, adding chemicals, and so on.
ENGLISH
PARAMETERS
VALUES
Control Mode
FLOW/SPEED
S5-S8
5 - 25 m3/h (o
20 - 110 GPM)
20% - 100%
The speeds from 5 to 8 cannot be loaded from the keyboard, but they are
activated and deactivated only by the TIMERS system (paragraph 5.6).
Unlike speeds 1-4, they do not have any associated duration, as the
activation time is decided always and only by the TIMERS.
PARAMETERS
VALUES
Control Mode
FLOW/SPEED
X1-X4
5 - 25 m3/h (o
20 - 110 GPM)
20% - 100%
STOP
Speeds X1-X4 do not have their own associated duration, but are
activated and deactivated according to external input signals.
PARAMETERS
VALUES
SPEED
20% - 100%
TIme
1 min - 10 h
65
DESCRIPTION
The first choice to make is whether
you want the setpoints "SET1-4" to
set the system regulation mode to
"Flow" or "Speed %" (see paragraph
3.1.1).
Setting the speed with flow control.
Setting the speed with fixed curve
control (in percentage%)
DESCRIPTION
The first choice to make is whether
you want the setpoints "SET1-4" to
set the system regulation mode to
"Flow" or "Speed %" (see paragraph
3.1.1).
Setting the speed with flow control.
Setting the speed with fixed curve
control (in percentage%)
Setting of the speed "0" (STOP),
useful for the connection of a
possible float or safety switch in
OVERRIDE mode
DESCRIPTION
Setting the speed with fixed curve
control (in percentage%)
Setting the duration time at the
relative speed.
The duration value indicates the
time that the speed remains active,
after which it ends; if you want the
speed to remain always active
without interruption, the duration
must be programmed as "Endless".