GB
ENGLISH
in
=10, 11, 12,
No action
(2)
13 Kiwa function
(low input pres-
sure signal)
PR=0
No action
Remote pres-
sure sensor
disabled
PR=1
No action
Use of remote
pressure sensor
Tab.5 Triggering of safety mode
The activation of the function relating to this box + any other function in
(1)
safety mode triggers a system stop. In this case, the system displays the
highest priority stoppage cause.
The numbers separated by commas indicate the possible setting values
(2)
for the function concerned
In the event of a communication fault, the control unit activates relay 1.
5.1.4 - Connection to more than one control unit
Up to 2 control units may be used simultaneously, provided one of them
is PWM Com type and the other either e.sylink or PWM IO.
An e.sylink and a PWM IO control unit may not be used simultaneously.
If 2 control units are used simultaneously, the inputs to be connected are
as shown in the table below
Control units connected to the
e.sybox system
PWM Com+e.sylink
PWM Com+PWM IO
Tab.6 Control unit to which the inputs must be connected (if the e.sybox is used
with 2 control units)
78
System in
No action
System in
stop status F4
stop status
No action
No action
No action
Setpoint
No action
Remote
on remote
setpoint
sensor
ignored
Device to which the Inputs must be
connected
e.sylink
PWM IO
N.B.: The PWM Com control unit does not have a pressure input, so
(1)
if only this control unit is used, the remote setpoint function cannot be
utilised.
5.1.5 - Control unit function setup
The default value of all the inputs and the remote pressure sensor is
DISABLE, so before they can be used, they must be activated by the
user; see point 7.6.15 - Setup of auxiliary digital inputs IN1, IN2, IN3, IN4,
pressure sensor point 7.5.6 - PR: Remote pressure sensor.
The outputs are enabled by default, see output functions point 7.6.16 -
Setup of outputs OUT1, OUT2.
If no control unit has been associated, the input, output and remote pres-
sure sensor functions are ignored and have no effect, regardless of their
setups.
The control unit parameters (inputs, outputs and pressure sensors) can
be set even if the connection is down or even not made.
If the control unit is associated (it is included in the e.sybox's wireless
network) but is not present or not visible due to problems, when the pa-
rameters related to these functions are set at a value other than disable
they blink to indicate that they will not be able to fulfil their functions.
5.1.6 - Association and disassociation of e.sybox and control unit
The procedure for associating a control unit to an e.sybox is the same as
for associating an e.sybox:
locate the AS page of the installer menu and hold down the "+" key for 5
sec., until the blue LED blinks (whether the e.sybox is stand-alone or in a
group). After this, press the ► key for 5 sec. until the blue communication
LED starts to blink. As soon as the connection has been established, the
LED becomes steady and the e.sylink symbol appears on the AS page of
the e.sybox.
The procedure for disassociating the e.sylink is the same as for the
e.sybox: locate the AS page of the installer menu and hold down the "-"
key for 5 sec; this will eliminate all the wireless connections present.