2.4 Electrical connection to the supply line
To improve immunity to the possible noise radiated towards other appliances it is recommended to use a separate
electrical duct to supply the product.
Attention: always respect the safety regulations!
Electrical installation must be carried out by an expert, authorised electrician, who takes on all
responsibility.
The system must be correctly and safely earthed as required by the regulations in force.
The
mains
Connect to the mains with a two-pole switch, with contact opening distance of at least 3 mm.
The
thermal
The leakage current to earth is max. 3.5 mA. It is recommended to use a type F differential switch. The
system must be adequately sized. The pump must be fed by means of an isolation transformer or a
differential switch, which must have a differential operating current no higher than 30 mA.
The mains terminals may still have dangerous voltage when the motor is stopped and for a few minutes
after disconnecting from the power mains.
The line voltage may change when the electropump is started. The line voltage may undergo variations
depending on other devices connected to it and on the quality of the line.
In the case of electropumps without a cable, provide power cables type H05 RN-F for internal use and
type H07 RN-F for external use, complete with plug (EN 60335-2-41). If the power cable is damaged, it
must be replaced by the manufacturer or by their authorised technical assistance service, so as to avoid
any risk.
voltage
must
be
magnetic
circuit
breaker
ENGLISH
Figure 3
the
same
as
that
and
the
power
46
on
the
motor
cables
must
be
correctly
data
plate.
sized.