Snap-On ECO DUAL GAS Manuel D'instructions page 49

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

INSTRUCTIONS MANUAL
Set HVAC blower motor on low, A/C switched off, air distribution mode set to "flor2, then press
ENTER to continue
DD/MM/YY XX:XX PM
ESC
Put a SAE J2913 compliant leak detector
set to high-maximum sensitivity (4g/year)
into the center of a floor duct outlet, as
far as possible
ENTER
Put a SAE J2913 compliant leak detector set to high-maximum sensitivity (4g/year) into the
center of a floor duct outlet, as far as possible, then press ENTER to continue
DD/MM/YY XX:XX PM
Was this test performed?
YES
NO
A pop-up message is displayed asking confirmation, press YES or NO to continue:
DD/MM/YY XX:XX PM
Was a leak found?
YES
NO
Press NO if no leak was found, the following screen will be displayed:
DD/MM/YY XX:XX PM
Is there an auxiliary
evaporator?
YES
NO
Select YES to perform a leak check on the auxiliare evaporator:
49