Press ENTER to confirm, and insert the value into the GAS FILLING field.
NOTE: if gas filling is lower than 100 grams the following popup warning will be displayed:
Gas filling lower than 100 grams is not allowed, press ENTER then digit an higher amount of
gas filling.

START AUTOMATIC PROCEDURE:

After selected all the procedure data, press OK to continue
NOTE: the STOP button
possible to exit to the main menu from all the procedure except the recovery and the charge
ones. This because by not completing a recovery procedure it is possible that some refrigerant
remain in the internal circuit and it may compromise the next procedure. In the final phase of
the charge the procedure hasn't to be paused or stopped to avoid to compromise the precision
of the procedure.
The machine will test the purity of the refrigerant gas in the A/C system before beginning
recovery. Contaminated refrigerant cannot be recovered, since it would contaminate all the
refrigerant contained in the storage bottle. Purity testing is conducted after a sample of the
refrigerant gas to be analyzed is taken.
The following screen will be displayed:
INSTRUCTIONS MANUAL
DATABASE
BMW
I3 (I01)
ALL;3447
2013-
R134A: 750 g
Press ENTER to continue
Charge amount
Less than 100g/4oz
or unavailable quantity requested
Press ENTER to continue
(min 100g)
literally pause the running procedure. From the pause it is