2. Intended use

With a danger and risk analysis, dangers created in the installation can be ascertained. If a dangerous situation
is to be avoided, then the sounders can be used as an integral part of a technical safety system (Safety Instru-
ment System - SIS) up to safety integration level 2 (SIL 2).
Because of the very different integration of the sounders in various safety architectures, they must be viewed
differently. The following uses are described in the safety manual:
Use as a starting alarm of machines or similar applications (see section 4.4.1 )
Use as a warning system without automatic test function via a superior control (see section 4.4.2.1)
Use as a warning system with automatic test function via a superior control (see section 4.4.2.2 )
In general, the operational safety of the device and the therefore connected system is only guaranteed during
intended use in accordance with the specifications of the operating manual. Custom-designed dangers could
result from inappropriate or unintended use of this device.

3. Technical data

3.1. Installation drawing

Fig. 3

3.2. Electrical data

Nom. voltage
Voltage range
Current consumption
Current consumption monitoring circuit
Control current option TAS
Capacity of failure contact
Duty cycle
Life time

3.3. Mechanical data

Degree of protection
Protection class
Mounting position
Cable entry
Clamp range of cable gland
Terminals
Weight
Material of housing
Surface coating
Datei/ file name:085501958e.docx
Ø7
M20x1,5
Blanking plug M20
Seite / page: 21 / 52
143
Fixing bolt e.g. 2x M6x20
DS10
230V AC
95 .. 253V AC
60 mA @ 230V
30mA @ 230V
Solid state relay
A replacement of the device is recommended after 20 years or
2500 operating hours.
IP 66 / 67 ( EN 60529 )
Opening of bell mouth shall not point upwards
Cage Clamp 0,08-2,5mm² (AWG28-12),
(AWG12 THHN,THWN)
Al- die cast GD-Al Si12 Cu
Anodised, Polyester resin varnish, RAL 3000 - flame red
DS5
230V AC
95 .. 253V AC
40 mA @ 230V
<5mA (230V)
max. 230V~/80mA
R
<35Ω
DSON
100 %
I
2x M20x1,5
8 – 12 mm
1,95 Kg
Zeichnungsnr./ Drwg-no.: 30007-008-13e