Use As An Acoustic Warning System In One-Channel Version; Use As Acoustic Warning System Without Test Function - Pfannenberg DS5-SIL Instructions De Service

Sirène surveillée
Masquer les pouces Voir aussi pour DS5-SIL:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4.4.2. Use as an acoustic warning system in one-channel version

The function of the acoustic warning system is to be assessed as a safety function in the use as a warning sys-
tem after recording dangerous conditions. A measurement records a dangerous condition and introduces the
safe condition by controlling the acoustic warning system (personnel/operator is warned).
Note: The warning of people is a voluntary measure as it requires willing handling of one or more people. This
architecture only corresponds to the requirements of the European Machinery Directive if, according to state-of-
the-art technology, no constructive safety or other voluntary measure is possible to reach a safe condition.
The diagnosis can only be taken into account if there is regular, automated function checking, the minimum
interval of which must be in accordance with approx. ten to one hundred times the requirement rate according to
IEC/EN61508. This possibility is only available in low demand mode and is further described and evaluated in
section 4.4.2.2.
The acoustic warning system with diagnosis function is implemented as follows:
a) A measurement (input (1), logic (2)) records a dangerous condition and activates the acoustic warning
system (output (3))
b) The diagnosis (4) monitors the function of the acoustic warning system and reports OK to a superior
control system (5)
c) If an OK message takes place, then the superior control system (5) introduces the safe condition via
other measures (6).
Fig. 7 Warning system
Fig. 7. In section 4.4.2.2 th
e sounder partial systems (output - position 3) and diagnosis channel (diagnosis - position 4) are evaluated. It
should be noted that the sum of all PFH or PFD values must correspond to the required safety integration level
for the entire system.

4.4.2.1. Use as acoustic warning system without test function

The safety function – generating a warning signal – is realised via a one-channel system (1oo1 according to
IEC/EN61508) without taking account of the diagnosis function, as also described in section 4.2.
The low and high demand mode is useable in the system without the automatic test function.
Evaluation for applications with high requirement rate or continuous requirement (high demand) and low re-
quirement rate (low demand) without automatic test release of the monitoring equipment.
Datei/ file name:085501958e.docx
1
Recording
(Input)
5
Seite / page: 26 / 52
2
Evaluation
(Logic)
Superior
system
3
Output
(Output)
Diagnosis
4
(Output)
Output
6
Zeichnungsnr./ Drwg-no.: 30007-008-13e