operating voltage
Wire
pin
configuration external circuit
color
4)
3
green
GND
4
yellow
+ 24 V
Tab. 4:
Pin assignment - operating voltage
output signals to the control center (e.g. PLC) - (required for
analogue output option only)
Wire
pin
configuration external circuit / signal level
color
4)
8
red
Analogue
position
feedback +
7
blue
Analogue
position
feedback GND
Tab. 5:
Pin assignment - output signals of the control center - option
When the supply voltage is applied, the positioner is operating.
Actuate the automatic adjustment of the positioner, as described
in the chapter entitled "10.2 Automatic adjustment X.TUNE".
The indicated colors refer to the connecting cable available as an
4)
accessory (919061).
16
24 V DC ± 10 %
3
max. residual ripple
4
10 %
8
+ (0/4 – 24 mA)
GND
7
english
Type 8696

Start-up

10 sTarT-up
10.1 safety instructions
Warning!
risk of injury from improper operation.
Improper operation may result in injuries as well as damage to the
device and the area around it.
▶ Before start-up, ensure that the operating personnel are familiar
with and completely understand the contents of the operating
instructions.
▶ Observe the safety instructions and intended use.
▶ Only adequately trained personnel may operate the equipment/
the device.
10.2 a utomatic adjustment X.TUNE
To adjust the positioner to local conditions, the X.TUNE
function must be run following installation.
Warning!
danger due to the valve position changing when the X.TUNE
function is running.
When the X.TUNE is running under operating pressure, there is an
acute risk of injury.
▶ Never run X.TUNE while a process is running.
▶ Take appropriate measures to prevent the equipment from being
accidentally actuated.

Publicité