Honeywell IAQPoint2 Guide De Démarrage Rapide page 44

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

IAQPoint2™
Configure\Configure Display\Easy Temp Adj
If desired, a "Set" button can be displayed on the main menu, allowing the
temperature setpoint to be changed without entering a password� By default, this
feature is disabled� This feature is disabled by default and is only available on
models with the temperature sensor and the BACnet/Modbus interface�
Configure\Configure LonWorks [or] Configure Fieldbus
Models with the LonWorks interface will display this screen:
Configure LonWorks
Neuron ID
0700 0FF7 F600
Send Service Msg.
The following screen is available only on models with the BACnet/Modbus
interface� The monitor's fieldbus configuration options apply only to RS-485-
enabled units�
Configure Fieldbus
Protocol: Modbus
Baudrate: 9600
Address:
1
ID: n/a
Parity: Even
The monitor will reboot whenever the [
communication parameters will be implemented correctly�
Configure\Configure Fieldbus\Set Protocol
The monitor can be configured for either BACnet or Modbus from the Set Protocol
screen� The default is Modbus�
If the monitor is to communicate with the Honeywell Analytics 301C controller, this
screen should be configured for Modbus, 9600 baud, and no parity� The address
must be unique� If the monitor contains the optional temperature/humidity sensor,
the next two higher addresses should not be used�
Configure\Configure Fieldbus\Set Fieldbus Speed
The data rate of the fieldbus (from 4800 to 115200 baud) is selected at this screen�
This value must match all of the other devices on the segment�
38
] button is pressed so that the new