Remote Sensor Specifications - Honeywell IAQPoint2 Guide De Démarrage Rapide

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Specifications

Remote Sensor Specifications

Power:
Operating temperature:
Operating humidity:
Sensor type:
Visual indicator:
Size (DxWxH):
Weight:
Detection Ranges and Alarm Levels
Gas Detected
CO
Carbon monoxide
H
S
Hydrogen sulfide
2
NO
Nitrogen dioxide
2
O
Oxygen
2
COMB
Combustibles
Maximum Overload is the sensor exposure to gas concentration that
may result in permanent damage to the sensor.
34
Electrochemical sensor: 10-24 VDC, 50 mA
Catalytic: 10-16 VDC, 100 mA
-20 to 50°C (-4 to 122°F)
15 to 90% relative humidity (non-condensing)
Electrochemical cell (CO, NO
(Comb)
Amber LED (Tx)
3.5 x 4.5 x 6.5 cm (1.36 x 1.75 x 2.56 in.)
38 g (1.34 oz.)
Range
Alarm A
0-250 ppm
25 ppm
0-50 ppm
10 ppm
0-10 ppm
0.7 ppm
0-25 %vol
19.5 %vol.
0-100 %LEL
25 %LEL
E
, H
2
Alarm B
100 ppm
15 ppm
2 ppm
22 %vol.
50 %LEL
Point Standalone Gas Monitor User Manual
3
S, O
); catalytic
2
2
Maximum
Alarm C
Overload
225 ppm
500 ppm
20 ppm
150 ppm
9 ppm
1000 ppm
22.5 %vol
100 %vol
90 %LEL
100 %LEL