IAQPoint2™
units without the optional temperature and humidity sensor, lines three through five
contain "TRH Sensor Not Fitted�"
Line six conveys the period of the occupied timer and the relay source� The
occupied timer period can be set from 1 minute to 2 hours in six steps� The relay
source indicates the function of the optional relay� It can be configured to respond
to the gas level, to the digital fieldbus, or to the occupied timer�
Review\Status
The Status screen shows temporary information about the IAQPoint2 monitor�
The first line shows how many seconds the monitor has been running since the
last power interruption� The second shows whether the optional relay has been
detected� If the monitor is configured with a VOC sensor, line three displays the
raw signal from it� This number decreases when volatile organic compounds are
detected and can be useful for sensor verification�
Review\BACnet Config.
BACnet Config.
Location
"location"
Object Names
0 GAS_RDG_AI
1 TEMP AI
2 RH_AI
3 GAS_SPT_AV
4 TEM_SPT_AV
5 RH_SPT_AV
6 IAQ_GOOD_BI
7 OVDTIMER_BI
8 RLY_DRV_BO
9 OCC_DRV_BO
This screen displays the names of the ten BACnet objects and the device location�
These are writable over the network�
Configure menu
Configure
SetPoints
Outputs
Display
Fieldbus
Passwords & Reset
The monitor's customization begins with the Configure menu� The setpoints option
is available only with digital monitors and monitors equipped with relays� The
fieldbus option is available only with digital monitors�
32