Gas Monitor - Quick Start Guide
3
®
The E
Point
gas detection system combines a gas sensor (electrochemical or catalytic
3
®
type), a control unit, a buzzer, a relay, and RS-485 in one reliable and robust product.
The polycarbonate housing is resistant to rust, dents, and corrosion. It is well suited
for commercial use in certain outdoor environments and indoor environments such as
parking garages and mechanical rooms.
Installation
The main installation considerations are height and detection objectives. If the primary
application is the fastest possible leak detection, mount the sensor near the potential
leak sources. As a result, the indicated concentration may not be representative of
personnel exposure, and easy access for the required calibration and maintenance
can be compromised. If there are fans, wind, or other sources of air movement, gases
may tend to rise or collect in certain areas of a facility. The local air currents should be
assessed when selecting a sensor location. Air convection is often more important in
determining gas concentration areas than vapor density factors. As a rule, at least one
sensor should be located close to each point where an emission is likely to occur. The
detector must be easily accessible for calibration and maintenance.
If personnel protection is the primary application, mount the unit in the "breathing zone"
(3.5 to 5 ft., 1 to 1.5m) from the ground, within the range of a person's respiration area.
Protect the sensor from water, wash-down, and excessive humidity. To prevent electrical
interference, keep sensor and wire runs away from mercury vapor lights, variable speed
drives, and radio repeaters. Protect the sensor from physical damage (fork lifts, etc.). Do
not mount the sensor over a door in a refrigerated area. For critical locations, more than
one sensor should be installed in each room.
Never mount the sensor flat on a ceiling or on a vibrating surface.
Relative
Detected Gas
Density
Installation Height
(air = 1)
CO
Carbon monoxide
0.968
1–1.5 m (3–5 ft.) from floor
H
S
Hydrogen sulfide
1.19
30 cm (1 ft.) from floor
2
NO
*
Nitrogen dioxide
1.58 (cold)
30 cm–1 m (1–3 ft.) from ceiling
2
O
Oxygen
1.43
1–1.5 m (3–5 ft.) from floor
2
Most combustibles are heavier than air, with the exception of methane,
hydrogen, ethylene and acetylene. Sensors for gases that are heavier
Combustibles
than air should be installed approximately 30 cm (1 ft) from the floor. For
combustibles that are lighter than air, sensors should be installed 30 cm
(1 ft) from the ceiling, close to the potential leak source.
* May differ in certain applications. Hot NO
from exhaust systems is lighter than ambient air.
2
Duct Mounting
The E
3
Point
®
gas detector must be duct mounted using the custom housing provided
with the duct mount version. All of the components housed within the housing are factory
assembled. Gas detection in ducts works best for airflows between 500–4000 fpm.
Air flow
Air intake tube
E Point monitor
3
Air exhaust tube
Duct mount housing
Housing cover
1. Measure and mark the holes for int ake and exhaust tubes.
2. Drill the holes in the duct for the sampling tubes (1 1 / 2 in. (38 mm) for the air intake
tube, 1 / 2 in. (13 mm) for the air exhaust tube).
3. Affix intake and exhaust tubes to the duct mount housing.
4. Insert the tubes into the holes in the duct.
5. Orient the air holes on the air intake tube to face the airflow.
6. Attach the housing to the duct with four 8 x 3 / 4 " galvanized or zinc-plated sheet
metal screws (not provided).
7. Remove one of the knockouts (depending on where cables will enter the housing)
and affix appropriate conduit.
8. Run wiring through the conduit and the housing to the monitor.
9. Connect the wires (see the appropriate section below).
10. Screw the cover onto the monitor and replace the housing cover.
Wall Mounting
Mounting is usually done on concrete walls or columns, but the unit can be mounted
on any vertical surface or to a standard electrical
junction box. The housing is designed with spacers
on the back to allow moisture to flow behind the
housing without affecting the unit. Mounting holes are
located inside the housing.
1. Open the unit and drill the holes, as shown in the
illustration, (4 3 / 8 " (11.1 cm) apart if mounting
8.3 cm
directly to a wall, or with the height 3.281" (8.3
(3.281")
cm) for electrical boxes. Do not remove the PC
board when removing knockouts.
2. Mount the unit securely using appropriate
screws and anchors. The unit is designed to use
#6 screws.
3. Tighten to 8.7 in-lb (1 Nm) maximum.
4. Close the unit cover and tighten the cover screws to 29.7 in-lb (3 Nm).
Wiring
Power wiring must comply with all applicable codes, but never should be less than #20
AWG; 120 VAC wiring should be #14 or #12 AWG. Signal wiring should be done with
#20-24 AWG shielded twisted pair cable Belden 9841 or similar. Network units should
have no more than 2,000 ft (600 m) of #22 AWG wire. Smaller gauge sizes are limited
by the same resistance limit. Power wiring should never be less than #20 AWG. 120 VAC
wiring should be #14 or #12 AWG. Power wiring is grounded at the screw and nut on the
grounding plate inside the case.
Wiring Standalone Units
Ground the shield at the main control panel. Connect the shield wire in the sensor
terminal block labeled "shield. " Tape all exposed shield wire at the sensor to insulate it
from the enclosure.
Electrical Power:
24 VDC/VAC nominal, 0.35 amp maximum. Either AC or DC may
be connected to the terminal block.
Output: Circuit board mounted sensor provides a linear 4-20 mA output. Monitoring
equipment may have a maximum impedance of 500 ohms.
Circuit Board Connections: Connect the power wiring to terminal J1, communication
wiring to terminal J2, and external devices (ventilators, strobes, etc. to relay terminals
J5 or J6).
Relay Output: 2 DPDT relays, 5A @ 250VAC
3-Wire Current Sink Output (DC supply only)
J5, J6 RELAY OUTPUTS
6
5
Duct
J2
J1
V+
V-
SIG
RTN Vcc
A
B
GND/
Shld
To remote sensor
+
-
- + - + - + -
24 VDC
DDC SYSTEM
English
4-wire Current Sink Output
1998-0767 Revision 4, March 2014
11.1 cm (4 3/8")
120 VAC Connection
Risk of electric shock
The transformer is mounted under the PCB and connections to the power terminal are
factory wired. Connect the live and neutral wires, as shown (ensure that power is off
before attempting to connect the wires). Replace fuse with same type: 1A 250 VAC, T.
Connecting a Remote to the Main Unit
Signal wiring should be done with #20-24 AWG shielded twisted pair cable Belden 9841
or similar. Remote sensors should have no more than 200 ft (61 m) of #22 AWG wire.
Smaller gauge sizes are limited by the same resistance limit.
The OUT1 and OUT2 connectors on the remote sensor's terminal are not used. Do not
connect wires to these locations.
SIG RTN Vcc
A
B GND/Shld
4
2
3+5
Normally
open
4+6
Normally
1+3
closed
2+4
3
1
Wiring Network Units
!
ALWAYS RESPECT MINIMUM
VOLTAGE REQUIREMENTS AT DEVICE
J5
J6
J2
J1
V+ V-
A
B
GND/
Shld
N.O. N.C.
N.O. N.C.
+
POS
-
24 VDC
NEG
Ground the shield at the main control panel. Connect the shield wire in the sensor
terminal block labelled "shield. " Tape all exposed shield wire at the sensor to insulate it
from the enclosure.
Main circuit board connections:
1. Connect power wiring to terminal J1
2. Connect Communication wiring to terminal J2
3. Connect external device (ventilator, strobe, etc) to relay terminal J5
User Interface
The E
3
Point
®
gas monitor is equipped with a 2-line, 8-character LCD screen that
displays reading information and serves as an interface for programming functions and
calibration.
Enter key: confirms selections and provides access to the programming menus
Escape key: cancels modifications and exits menus
LCD screen: displays the readings in real
time, including the type of gas detected,
the concentration, and measurement
value (% or ppm) and for which sensor
(built-in or remote)
Navigation controls: increment/decrement
values and allow scrolling through menus
LED
Description
Indicators
I/O
Standalone:
1
Network:
Standalone:
Remote Sensor
2
Network:
Detection Ranges and Alarm Levels
Gas Detected
CO
Carbon monoxide
H
S
Hydrogen sulfide
2
NO
Nitrogen dioxide
2
O
Oxygen
2
COMB Combustibles
*Sensor exposure to gas concentration that may result in permanent damage to the sensor.
Limited Warranty
Honeywell Analytics, Inc. warrants to the original purchaser and/or ultimate customer ("Purchaser") of Honeywell products ("Product") that if any part thereof proves
to be defective in material or workmanship within one (1) year, such defective part will be repaired or replaced, free of charge, at Honeywell Analytics' discretion if
shipped prepaid to Honeywell Analytics at 4005 Matte Blvd., Suite G, Brossard, Quebec, Canada, J4Y 2P4, in a package equal to or in the original container. The
Product will be returned freight prepaid and repaired or replaced if it is determined by Honeywell Analytics that the part failed due to defective materials or workman-
ship. The repair or replacement of any such defective part shall be Honeywell Analytics' sole and exclusive responsibility and liability under this limited warranty.
Re-Stocking Policy
The following re-stocking fees will apply when customers return products for credit: A 15% re-stocking fee will be applied if the product is returned within 1 month
following the shipping date. A 30% re-stocking fee will be applied if the product is returned within 3 months following the shipping date. A full credit (less re-stocking
fee) will only be issued if the product is in perfect working condition. If repairs are required on the returned product, the cost of these repairs will be deducted from the
J5
credit to be issued. No credits will be issued beyond the three month period.
J5 RELAY OUTPUTS
6
4
2
Normally
3+5
Exclusions
open
4+6
If gas sensors are part of the Product, the gas sensor is covered by a twelve (12) month limited warranty of the manufacturer.
Normally
1+3
closed
2+4
If gas sensors are covered by this limited warranty, the gas sensor is subject to inspection by Honeywell Analytics for extended exposure to excessive gas concentra-
N.O.
N.C.
5
3
1
tions if a claim by the Purchaser is made under this limited warranty. Should such inspection indicate that the gas sensor has been expended rather than failed
prematurely, this limited warranty shall not apply to the Product. This limited warranty does not cover consumable items, such as batteries, or items subject to wear or
periodic replacement, including lamps, fuses, valves, vanes, sensor elements, cartridges, or filter elements.
Warranty Limitation and Exclusion
Honeywell Analytics will have no further obligation under this limited warranty. All warranty obligations of Honeywell Analytics are void if the Product has been subject
to abuse, misuse, negligence, or accident or if the Purchaser fails to perform any of the duties set forth in this limited warranty or if the Product has not been operated
in accordance with instructions, or if the Product serial number has been removed or altered.
Disclaimer of Unstated Warranties
The warranty printed above is the only warranty applicable to this purchase. All other warranties, express or implied, including, but not limited to, the implied warran-
ties of merchantability or fitness for a particular purpose are hereby disclaimed.
Limitation of Liability
It is understood and agreed that Honeywell Analytics' liability, whether in contract, in tort, under any warranty, in negligence or otherwise shall not exceed the amount
of the purchase price paid by the purchaser for the product and under no circumstances shall Honeywell Analytics be liable for special, indirect, or consequential
damages. The price stated for the product is a consideration limiting Honeywell Analytics' liability. No action, regardless of form, arising out of the transactions under
this warranty may be brought by the purchaser more than one year after the cause of actions has occurred.
Return to ToC Page
LCD screen
LED indicators
Escape
Navigation
key
controls
Enter
key
Display Modes
Always on = Normal operation
Power
Always off = microcontroller fault or no power
Blinking (twice per second) = self test
Always on = Alarm A triggered
Built-in Sensor
Slow blink (once per second) = Alarm B/C triggered
Fast blink (4 times per second) = Fault
Built-in Sensor
Always off = normal operation
Alarm A
Always on = Alarm A triggered
Slow blink (once per second) = Alarm B/C triggered
Fast blink (4 times per second) = Fault
Always off = normal operation
Always on when transmitting, blinks for communication
Transmit
Always off = normal operation
Maximum
Range
Alarm A
Alarm B Alarm C
Overload*
100 ppm
0-250 ppm
25 ppm
225 ppm
500 ppm
0-50 ppm
10 ppm
15 ppm
20 ppm
150 ppm
0-10 ppm
0.7 ppm
2 ppm
9 ppm
1000 ppm
0-25%vol
19.5%vol.
22%vol.
22.5%vol
100%vol
0-100%LEL
25%LEL
50%LEL
90%LEL
100 %LEL