Dimensions

3.0 in.
(77 mm)
6.4 in.
(163 mm)
Figure 8. Monitors' dimensions

Wiring and installation

IAQPoint2 models are available for wall-mounting or duct-mounting� Wall-mount
units can be installed on standard single-gang junction boxes� Locate the monitor
in an area easily accessible by a technician� Avoid locations in which the monitor
will be subjected to vibration or rapid temperature fluctuations� Follow local
regulations and site requirements� Position wall-mounted monitors at least 10 feet
(3 meters) from any air outlets� Install duct-mounted monitors in return-air ducts
(not in supply-air ducts)�
NOTE
!
Analog models are configured to source current only�
NOTE
!
Non-display models cannot be configured by users� If the
CO
sensor is fitted, the full scale value will be 2000 ppm�
2
Additionally, if the relay is present, the setpoint will be 850 ppm�
If the VOC sensor is fitted, the relay setpoint will be 50%�
The monitor is supplied as part of an installation kit containing:
• IAQPoint2 monitor
• backplate
• two plastic anchors w/screws
• Quick Start Guide (one page, paper)
• Resource CD
1 Wiring labels are of EIA485 standard�
1.5 in.
(38 mm)
3.0 in.
(77 mm)
8.7 in.
(222 mm)
IAQPoint2™
1.3 in.
(33 mm)
3.0 in.
(77 mm)
4.6 in.
(118 mm)
1
4.6 in.
(118 mm)
11