Fuel Conversion

The engine of your generator system is factory calibrated
to run on natural gas (NG) or on liquefied petroleum (LP)
vapor. To convert to either fuel, follow these steps:
NOTICE Units are set to NG at the factory.
1. Put the key into the lock of the front panel. Lightly
push down on the roof above the lock, and then
turn the key one quarter turn clockwise.
2. Lift the roof to the open position.
3. Push the control board OFF button.
4. Remove 15-amp fuse from the control panel.
5. Remove the rear panel.
6. Find the fuel selector switch (A) on top of the fuel
regulator (B).
Option A:
• Use a 5 mm hex wrench and turn the selector
switch to LP or NG.
• Install the tamper-proof plug (supplied) over fuel
selector switch. Make sure that the convex side
points out.
A
B
Option B:
C
Option B:
• Remove cap (C) from Fuel Select Valve by
sliding it upward.
• LP or NG is selected by using the cap (C)
as a tool to rotate the indicator to the LP or
NG mark (the image below shows the FSV
set to LP fuel).
• Install the cap (C) after fuel selection is
complete.
7. Once the fuel selection is complete, apply
a drop of cyanoacrylate (super) glue on
the Fuel Select Cap (C) before installing it
again.
8. Install the rear panel.
9. Install 15-amp fuse in the control panel.
10. Push the control board AUTO button.
11. Close the roof.
Option A:
C
19