4.6
Multifunctional display
4.6.1
LCD lighting
The backlight lamp is managed by the Gen-set control module, which switches off the backlight after a
programmable time (P.492) if no buttons are pressed in the meantime. Press any button to switch the
lamp ON again, (we recommend using the SHIFT
This
4.6.2
Contrast
The contrast can be adjusted by pressing the SHIFT
contrast or the SHIFT
Signalling
Function
Network/Bus mains power is OFF or MAINS SIMULATION digital
input is disabled.
Mains power is ON and stable in the range of tolerance, or MAINS
SIMULATION digital input is enabled from the set time.
MAINS LIVE
Flashes at 50% during transition between the previous two states.
Generator voltage and frequency are not present.
Generator voltage and frequency are present and stead within the
GENERATOR
tolerance range.
LIVE
Flashes at 50% during transition between the previous two states.
The engine is OFF.
ENGINE
The engine is running
RUNNING
Cooling phase
The MCB is open.
The MCB is closed
Flashes at 25% ON if open after a closing command.
MCB
Flashing at 75% ON if closed after an opening command.
Flashing at 50% in synchronization phase with BUS LIVE indicator.
The MCB is open.
The MCB is closed
Flashing at 25% ON if the KG is open after a closing command.
GCB
Flashing at 75% ON if closed after an opening command.
Flashing at 50% in synchronization phase with BUS LIVE indicator.
function
can
be
+RIGHT
button as it has no function when used alone).
disabled
by
setting
+ LEFT
buttons to increase it.
parameter
P.492
to
buttons to decrease the
User's Manual HT DST4602
0.
9