The following table provides an overview of typical conductor cross-sections
(copper cable with PVC insulation, 30 °C ambient temperature, continuous
mains current max. 100% nominal input current). Actual mains cable cross-
section requirements may deviate from these values depending on actual
operating conditions.
Mains connection
AEC 401
-19
9.7 kVA
-21
12.5 kVA
-22
15.2 kVA
-23
17.3 kVA
-25
22.2 kVA
-27
27.7 kVA
-29
31.2 kVA
-31
41.6 kVA
-33
52.0 kVA
-35
62.3 kVA
-37
76.2 kVA
-39
86.6 kVA
-43
103.9 kVA
-45
124.7 kVA
-47
145.5 kVA
-49
173.2 kVA
-51
160 kVA
-53
200 kVA
-55
250 kVA
-57
315 kVA
-59
355 kVA
-61
400 kVA
06/19
Mains cable
2.5 mm²
2.5 mm²
4 mm²
4 mm²
6 mm²
10 mm²
10 mm²
16 mm²
25 mm²
35 mm²
35 mm²
50 mm²
70 mm²
95 mm²
2x70 mm²
2x95 mm²
150 mm²
240 mm²
2x120 mm²
2x150 mm²
2x185 mm²
2x240 mm²
Quick Start Guide AEC
PE-conductor
2x2.5 mm² or 1x10 mm²
2x2.5 mm² or 1x10 mm²
2x4 mm² or 1x10 mm²
2x4 mm² or 1x10 mm²
2x6 mm² or 1x10 mm²
1x10 mm²
1x10 mm²
1x16 mm²
1x16 mm²
1x16 mm²
1x16 mm²
1x25 mm²
1x35 mm²
1x50 mm²
1x70 mm²
1x95 mm²
95 mm²
120 mm²
120 mm²
150 mm²
185 mm²
240 mm²