Last Error 310 facilitates troubleshooting and error diagnosis
with the shown error code.
The error message can be acknowledged via the control unit
buttons and digital input STO.
Key
Meaning
F00
00
No fault has occurred.
F05
00
Overcurrent; mains unit overloaded, check mains connection and filter.
07
Overcurrent, slow triggering by software.
F07
00
DC link voltage too high, check deceleration ramps and connected
brake resistor.
01
DC link voltage too low, check mains voltage.
F12 05
Fault message of 5-second monitoring. Shut-down paths S1IND and
S7IND were not actuated at the same time, but with an offset of more
than 5 seconds. Check addressing of shut-down paths or control of
protection provision.
06/19

Error messages

Output current
DC link voltage
Safety function STO
Quick Start Guide AEC