1.2 Designated use
The product is an electrical drive component. It is applicable for
installation in machines or electrical plants
industrial environments
1.3 Transport and storage
Ambient temperature:-25 ... 55 °C
GB
Relative humidity:
Store in original packaging in dry rooms without dust.
Avoid high temperature variations.
Connect to mains voltage for 60 minutes after one year of storage before
use.
1.4 After unpacking
Make sure that the delivered product is the part you have ordered.
Check if the product is damaged and make sure that the delivery is
complete.
File complaints with the supplier immediately.
1.5 Place of installation
In rooms without weather exposure.
Avoid direct sunlight exposure.
Avoid dust.
Keep away from strong electromagnetic fields.
Keep away from combustible material.
Provide sufficient cooling. Install fans when installing the frequency
inverter inside an enclosed cabinet.
Altitude: ≤4000 m, over 1000 m with derating (output current reduction).
The degree of protection of the device is IP20. Use of the device in
explosive atmospheres is not permitted.
1.6 Operational conditions
Ambient temperature: 0 ... 40 °C
Relative humidity:
Ambient pressure:
During Standard operation leakage currents > 3.5 mA can occur.
56
5 ... 95%, free of condensation.
maximum 85%, free of condensation
70 ... 106 kPa
Quick Start Guide AEC
06/19