Connection of precharging circuit (X1: X/C,
A
Y/D, Z)
Install separately from control cables.
B
DC link connection (X1: +, -)
B
Connect to a common direct voltage source.
Cable with a length >300 mm must be
shielded, the cable shield must be connected
to the mounting plate on both sides. Use
twisted cables where possible.
Control connection (X210A, X210B)
C
Control and signal cables must be kept
physically separate from the power cables.
Analog signal cables are to be connected to
the shield potential on one side.
D
Mains connection and connection of brake
D
resistor (X2)
Mains cable to be installed separate from
control and signal cables as well as DC link
connection.
Install radio interference filters at the mains input
of line chokes.
As from a length of 300 mm the cables
installed between radio interference filters,
line choke, sine filter and the mains unit must
be shielded. The shield is to be connected to
a PE bar properly using a suitable cable clamp
(large contact surface).
If a brake resistor is used, the connection
cable must be shielded, and the cable shield
is to be connected to earth potential on both
sides.