Connecting
3.2 Transmitter Wiring
3.2.1

Wiring Temperature Sensor to Transmitter

Wiring Temperature Sensor to the Analog Input Module
Hazard Voltage
Contact with exposed wiring will lead to fire, electric shock, or serious personal injury.
Set transmitter and instrumentation power to OFF when inserting or removing the Analog
Input Module, or when making connections to TB1, TB2, TB3 and TB4.
1. Disconnect power from the unit to the transmitter.
2. Open the transmitter top cover by releasing the cover latch.
3. Loosen the captive thumbscrew securing the Access Cover and remove Access Cover.
4. Using a flat-blade screwdriver, remove four captive screws securing the I/O board.
Remove board and set it aside.
Figure 3-2
24
DANGER
Analog Input Module Access
Access Cover Screw
Flow Meter
Power Switch
Latch
Access to Analog Input Module
FUS1010 IP65 NEMA 4X & IP66 NEMA 7 Quick Start
Operating Instructions, 07/2014, A5E03086486-AD