Operating instructions
Start-up
Open the gas remote switch if present.
1. Open the extraction valve.
2. If necessary (e.g. after a new installation), firmly press the
green reset button (crash sensor triggering element reset)
on the the MonoControl CS gas tank for about 5 seconds.
Figure 1
Checking for leaks in the high-pressure
section
The screw joints must be tested for leaks using suitable
means (such as a leak-finder spray in accordance with
EN 14291).
The operator is responsible for this.
12
1.
2.
Checking for leaks in the low pressure
section
(maximum test pressure 150 mbar)
The test must be conducted by a technician!
– Turn off all consumers.
– Open stop valves and, if present, the gas remote switch.
– Remove the threaded cap from the test connection (b) and
connect the test pump with test hose to the test connection.
Figure 2
– Carry out the check for leaks (e.g in Germany in accordance
with G 607).
– If the gas system leaks, close the extraction valve and have
the gas system repaired immediately by an expert. Do not
open the extraction valve until repair is complete.
– When testing is complete, screw the threaded cap back
onto the test connection.
b